Operating and Field Test Procedure

The Watts No. TK-7 Backflow Preventer Test Kit is especially

made to test the individual check modules of the Watts Series 7

residential dual check backflow preventers and can also be used

to test any double check valve backflow preventer, Series 709/

LF709 or 007/LF007. The test kit contains three segments of

durable shatterproof tubing, two brass adaptors used to assem-

ble the three tubing segments, and test hardware to enable

testing of Series 7 check modules and standard double checks.

A rugged simulated leather carrying case is provided for ease of

handling and compactness.

Specifications

• Total working height of tube - 44"
• Adaptors - (2) Brass, for Series 7 modules and double checks
• Tubing - Three segments of plastic tubing
• Moisture resistant instruction panel
• Case - Durable simulated leather - weather proof and mildew

proof

Case

Instruction

Panel

Water Column

Sight Tube

Adaptor for Testing

Series 7 Modules

Adaptor for

Testing Double

Check Valve

NOTICE

Backflow prevention assemblies

MUST be installed by a licensed

journeyman tradesperson, who is recognized by the authority

having jurisdiction, and inspected for compliance with local safety

codes. Certified testing and maintenance are required to ensure

proper function and maximum effectiveness of assemblies. These

services must begin upon installation and be provided at intervals

not to exceed one year and as system conditions warrant.

Instructions
No. TK-7

Backflow Preventer Test Kit

No. 7 Check Modules

Complete valve cannot be tested in the

line, however, each check module Part No.

SA7B16 can be tested individually as follows:

Module Test Procedure

Purpose: To test check valves for tightness

in the direction of flow.
Using Watts TK-7 test kit proceed as follows:
1. Remove first check module from valve

body and insert complete with O-ring in

plug module adaptor. Seat firmly with mov-

ing portion of check module facing up.

2. Assemble module adaptor hand tight to

bottom half.

3. Assemble 3 piece water column sight tube

in numerical sequence and attach to top

half of body module adaptor.

4. Holding in vertical position, fill sight tube

with water (no water leakage can be per-

mitted at sight tube joints).

5. Observe liquid level. Liquid level may

drop but as minimum water column of 28

inches (1.0psi) (6.9 kPa) or greater should

be maintained when the check module is

operating correctly. If water column falls

below 28 inches, check module is fouled

and should be replaced (See assembly

instructions).

6. Remove first check module from module

adaptor, and repeat above procedure with

second check module.

Adaptor for Testing

No. 7 Modules

Body Module

Adaptor

O-ring

1st or 2nd

Check Module

O-ring

Plug Module

Adaptor

Double Check

Adaptor

Threaded for

Connection to

Test Cocks

EZ-TC Adaptor

Adaptor for Testing

Double Check Valves

Field Testing Procedure

IS-TK-7

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information

can result in death, serious personal injury, property

damage, or damage to the equipment.
Keep this Manual for future reference.