Series LFMMV

Thermostatic Tempering Valves

Sizes:

1

2

",

3

4

", 1"

IS-MMV-M1

LFMMV-UT-M1

LFMMV-QC-M1

Triple Listed!

ASSE 1017,

ASSE 1069 & ASSE 1070

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-

mation can result in death, serious personal injury,

property damage, or damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing

codes prior to installation. If the information in this manual is

not consistent with local building or plumbing codes, the local

codes should be followed. Inquire with governing authorities for

additional local requirements.

WARNING

!

FAILURE TO COMPLY WITH PROPER INSTALLATION

AND MAINTENANCE INSTRUCTIONS COULD

CONTRIBUTE TO THE VALVE FAILURE, RESULTING IN

INJURY AND/OR DEATH.
TO ENSURE THE ACCURATE AND RELIABLE

OPERATION OF THIS PRODUCT, IT IS ESSENTIAL TO:
• Properly design the system to minimize pressure and tem-

perature variations.

• This valve is not factory preset and can be adjusted to

deliver scalding temperatures. Check outlet temperature

to ensure it does not exceed 105°F (41°C). Make sure

temperature limit stop is properly re-set to maximum 105°F

(41°C) following valve maintenance or repair. Tampering

with limit stop in any way may result in scalding temperature

causing serious bodily harm and/or death.

WARNING

!

WARNING

!

Need for Periodic Inspection and Yearly Maintenance:

Periodic inspection and yearly maintenance by a licensed

contractor is required. Corrosive water conditions

and/or unauthorized adjustments or repair could render

the valve ineffective for service intended. Regular check-

ing and cleaning of the valve’s internal components

and check stops helps assure maximum life and proper

product function. Frequency of cleaning and inspection

depends upon local water conditions.

*The wetted surface of this product contacted by consumable water

contains less than 0.25% of lead by weight.

Installation Instructions

Valve should be installed and adjusted by a licensed contractor

in accordance with local codes and ordinances. Further, this

valve should be installed in a location where it is accessible for

cleaning, service or adjustment.

1.

Close both the hot and cold water shutoff valves upstream

nearest to the intended installation.

2. Bleed the remaining water from the system.
3. Connect the water supply to valve as shown in Figure 1, 2 or

3 depending on application. Supply piping must be flushed

clean before making connections to the valve.

4. Valve can be installed in any position. The inlet hot supply is to

be connected to the “H” side of the valve, the cold supply side

to the “C” side and the mixed water outlet to the “M” side.

5. Make sure union nuts are placed over tailpieces prior to solder-

ing or threading to pipe.

6. For valves with Quick-Connect tailpieces refer to "Quick-

Connect Installation" instructions below

NOTICE

To prevent damage to valve from excessive heat during

soldering, remove unions and gaskets from valve body prior

to soldering.
7. After soldering, flush piping and install valve using filter wash-

er on hot and cold water inlet and fiber washer on the mixed

water outlet.

8. Start-up: Open cold water supply, then hot water supply.

Inspect for leaks.

9. Adjust temperature to desired setting (see Temperature

Adjustment Section). Watts recommends a maximum

temperature of 105°F (41°C) for shower and bathing fixtures.