Watts LFN36 User Manual

Model lfn36-m1, Lead free, Vacuum relief valve

Advertising
background image

For Water Heater/Tank Applications

ES-LFN36

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Model LFN36-M1

Vacuum Relief Valve

Sizes:

1

2

" –

3

4

" (15 and 20mm) Male NPT

Features

• Low profile
• All Lead Free* brass body
• Protective cap
• Suitable for low pressure steam and water service
• Tested and rated to ANSI Z21.22
• CSA certified
• The LFN36-M1 features Lead Free* construction to comply

with Lead Free* installation requirements.

Applications

• Domestic water heaters and supply tanks
• Table top heaters
• Jacketed steam kettles
• Unit heaters
• Low pressure steam systems
• Steam coil heaters
Note: Vacuum relief valves are not designed or approved as

backsiphonage backflow preventers. For protection against

backsiphonage install Watts Series 288A vacuum breakers.

Standards

Tested and rated to ANSI Z21.22
CSA certified

Specifications

A Watts Model LFN36-M1 Vacuum Relief Valve shall be installed

on domestic hot water supply tanks/ heaters/ unit heaters/

steam kettles as indicated on plans. The vacuum relief valve

shall be ANSI Z21.22 rated and CSA certified. The vacuum relief

valve shall have an all brass body and include a protective cap

for automatic venting of a closed system to atmosphere when

a vacuum is created. The Lead Free* Vacuum Relief Valve shall

comply with state codes and standards, where applicable,

requiring reduced lead content. The Watts LFN36-M1 Vacuum

Relief Valve permits air to enter and prevent vacuum condi-

tions that could siphon the water from the system, resulting in

collapse of a tank or water heater or equipment burn out. The

valve shall be a Watts Model LFN36-M1.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

LFN36-M1

Tested and rated under “ANSI Z21.22

Relief Valves for Hot Water Supply Systems”.

Design certified by

LFN36-M1

T&P

Relief

Valve

Hot

Cold

Tank

Figure 1

Domestic Hot Water Supply Tanks and Heaters with

Top Supply

LEAD FREE

*

* The wetted surface of this product contacted by consumable water

contains less than one quarter of one percent (0.25%) of lead by
weight.