Throttles to reduce high upstream pressure to

constant lower downstream pressure

Low Flow By-Pass controls at low flows

Main Line valve controls at high flows

Reducing and Low Flow By-Pass setpoints are

separately adjustable

(AOS)

P/L

2

3

4

CLOSES VALVE

OPENS VALVE

FLOW

X

X

X

1

Y/FC

F115-74 (Globe)

F1115-74 (Angle)

PRESSURE REDUCING CONTROL VALVE

with

LOW FLOW BY-PASS FEATURE

Operations

The Watts ACV Pressure Reducing Control Valve with Low Flow By-Pass is designed to automatically reduce

a fluctuating higher upstream pressure to a constant lower downstream pressure regardless of varying flow

rates. It is controlled by a normally open, pressure reducing pilot designed to: 1) Open (allowing fluid out of

the main valve cover chamber) when downstream pressure is below the adjustable setpoint, and 2) Close

(allowing fluid to fill the main valve cover chamber) when downstream pressure is above the adjustable

setpoint. A decrease in downstream pressure causes the valve to modulate toward an open position, raising

downstream pressure. An increase in downstream pressure causes the valve to modulate toward a closed

position, lowering downstream pressure.

A Low Flow By-Pass Valve is piped parallel to the Main Pressure Reducing Valve, and is set approximately

10 PSI higher. The Low Flow By-Pass handles flow requirements below the range of the Main Pressure

Reducing Valve. During “off peak” demand conditions, the Low Flow By-Pass provides flow and pressure

to the downstream zone. As flow requirements increase beyond the capacity of the Low Flow By-Pass,

downstream pressure falls below the setpoint of the Main Pressure Reducing Valve allowing it to throttle

toward open, supplementing flow and pressure. As flow requirements decrease, downstream pressure rises

above the setpoint of the Main Pressure Reducing Valve, causing it to throttle toward closed, allowing the Low

Flow By-Pass to resume command of flow and pressure.

1 – Main Valve (Single Chamber)

2 – Pressure Reducing Control

3 – Fixed Orifice

4 – Low Flow By-Pass