Watts FP53L User Manual

Model fp53l, Pressure relief valve, For fire protection applications

Advertising
background image

Model FP53L

Pressure Relief Valve

Size:

1

2

" (15mm)

Watts No. FP53L is designed for use in fire protection grid systems

to provide protection against excessive water pressure caused by

thermal expansion or line surge. It is available in 175psi (12.1 bar),

185psi (12.8 bar), 260psi (17.9 bar) and 310psi (21.4 bar) pressure

relief settings and can be installed horizontally or vertically. Bronze

body construction with stainless steel spring to inhibit corrosion. The

valve is constructed with a precision stem guide to ensure proper

reseating. The test lever affords periodic manual testing and flushing

of waterways and seating surfaces.

Features

• Underwriters Laboratory listed
• Forged stainless steel spring
• Bronze body construction for superior strength and to

prevent corrosion

• Manual test lever
• Valve stem is guided to enhance reseating

1

2

" (15mm) male inlet x female outlet

• Pressure settings: 175psi (12.1 bar), 185psi (12.8 bar),

260psi (17.9 bar) and 310psi (21.4 bar)

Specifications

For applications requiring a UL approved relief valve to provide

pressure relief protection from water pressure in excess of 175psi

(12.1 bar). Each valve shall be bronze body construction with forged

stainless steel spring. It shall have a test lever and the valve shall be

guided to enhance reseating and to decrease chance of the seat

being misaligned. Watts Model No. FP53L.

Dimensions — Weight

1

2

" NPT

Female Outlet

Model

Size

HeigHt

WidtH

WeigHt

in.

mm

in.

mm

in.

mm

lbs.

kgs.

FP53L

1

2

15

3

1

2

89

1

7

8

48

1

2

.23

Pressure Relief Valves should be tested periodically to ensure that

the product has not been affected by corrosive water conditions and

to ensure that the valve and discharge piping have not been altered

or tampered with.

1

2

" NPT

Male Inlet

For Fire Protection Applications

ES-FP53L

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

This device is designed for emergency safety relief and shall

not be used as an operating control.

NOTICE

This information is not intended to replace the full product

installation and safety information available or the experience

of a trained product installer. You are required to thoroughly

read all installation instructions and product safety informa-

tion before beginning the installation of this product.

WARNING

!

ES-FP53L 1414

© 2014 Watts

USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts
reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications
on Watts products previously or subsequently sold.

A Watts Water Technologies Company

Advertising