Watts 994 User Manual

Series 994, Lead free, Re duced pres sure zone assemblies

Advertising
background image

994OSY

Models

Suffix:
NRS –

non-rising stem resilient seated gate valves

OSY –

UL/FM outside stem & yoke resilient seated gate valves

**OSY FxG – flanged inlet gate connection and grooved outlet gate connection
**OSY GxF – grooved inlet gate connection and flanged outlet gate connection
**OSY GxG – grooved inlet gate connection and grooved outlet gate connection
LF –

without shutoff valves

S –

cast iron strainer

Available with grooved NRS gate valves - consult factory**

Post indicator plate and operating nut available - consult factory**

**Consult factory for dimensions
Note: The installation of a drain line is recommended. When in stall ing a drain line,

a 994AGK-P air gap is necessary. See ES-AG/EL/TC for additional information.

Series 994

Re duced Pres sure Zone Assemblies

Sizes: 2

1

2

" – 10" (65 – 250mm)

Series 994 Re duced Pressure Zone Assemblies are de signed to pro­

vide pro tec tion of the potable water supply in ac cor dance with na tion al

codes. This series can be used where ap proved by the local au thor i ty hav ing

ju ris dic tion on health hazard cross­con nec tions. Se ries 994 fea tures a short lay

length, light weight stain less steel body, cor ro sion re sis tant stainless steel

re lief valve, and patented tor sion spring check valves.

Features

•   Stainless steel construction provides long term corrosion resistance 

and maximum strength

•   Stainless steel body is half the weight of com pet i tive designs reducing 

installation & shipping costs

•  Short end-to-end dimensions makes retrofit easy
•   Bottom mounted relief valve reduces clearance re quire ments when

installed against an outside wall

•   Torsion spring check valves provides maximum flow at low 

pressure drop

•  Thermoplastic & stainless steel check valves for trouble-free operation
•  No special tools required for servicing
•  Compact construction allows for smaller enclosures
•   Stainless steel relief valve features a balanced rolling diaphragm to eliminate 

sliding seals and lower maintenance costs

Specifications

A Reduced Pressure Zone Assembly shall be installed at each cross­con­

nec tion to prevent backsiphonage and backpressure of haz ard ous ma te ri­

als into the potable water supply. The assembly shall consist of a pres sure

differential relief valve located in a zone be tween two pos i tive seating

check valves. The main valve body shall be man u fac tured from 300 Series

stainless steel for corrosion re sis tance. The check valves shall be of

thermoplastic construction with stain less steel hinge pins, cam arm, and

cam bearing. The check valve shall uti lize a single tor sion spring design

to minimize pressure drop through the as sem bly. The check valves shall

be modular and shall seal to the main valve body by the use of an O­ring.

There shall be no brass or bronze parts used with in the check assembly

or relief valve. The use of seat screws to re tain the check valve seat is

prohibited. All internal parts shall be ac ces si ble through a single cover on

the valve assembly se cure ly held in place by a two­bolt grooved coupling.

The dif fer en tial relief valve shall be of stain less steel con struc tion and shall

utilize a rolling di a phragm and no sliding seals. The relief valve shall be

bot tom mount ed and supplied with a steel reinforced sensing hose. The

assembly shall include two resilient seated shutoff valves & four ball type

test cocks. The assembly shall be a Watts Series 994.

Now Available

WattsBox Insulated Enclosures.

For more information, send for literature ES-WB.

IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES

FOR LOCAL INSTALLATION REQUIREMENTS

Test Cocks

Stainless Steel

Cover

Grooved Coupling

Disc

Replaceable

Seat

Torsion

Spring

Laser Cut/Polished

Cam Arm

Stainless Steel

Relief Valve

For Health Hazard Applications

ES-994

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor –––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval ––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative –––––––––––––––––––––––––––––––––––––––

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with­
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

* The wetted surface of this product contacted by consumable water

contains less than one quarter of one percent (0.25%) of lead by weight.

LEAD FREE

*