Series 9D

Dual Check Valve with
Intermediate Atmospheric Vent

Sizes:

1

2

"M3 (15mm),

3

4

"M2 (20mm)

Series 9D is specially made for smaller supply lines and ideally
suited for laboratory equipment, processing tanks, sterilizers,
dairy equipment and similar applications. It is particularly recom-
mended for boiler feed lines to prevent backflow when supply
pressure falls below system pressure.

Series 9D is suitable for use on hot or cold water and can be
used under continuous pressure. It features a primary check
valve utilizing a rubber disc seating against a mating rubber part
to ensure tight closing. A secondary check valve utilizes a rub-
ber disc-to-metal seating. In the event of fouling of the down-
stream check valve, leakage would be vented to atmosphere
through the vent port thereby safeguarding the potable water
system. Construction is brass body with stainless steel working
parts, integral strainer and durable rubber discs. Female union
inlet and outlet connections. Sizes

1

2

" (15mm) and

3

4

" (20mm).

Drain is

1

2

" (15mm) thread connection.

Features

• True line-sized construction allows the check modules to

open further allowing dirt and debris to pass more freely
reducing check fouling

• Stainless steel internal parts

• Maximum flow at low pressure drop

• Furnished with union connections to facilitate removal and

replacement for maintenance

• Compact for economy combined with performance

• Design simplicity for easy maintenance

• Can be installed vertically or horizontally

Specifications

For Backflow Preventers with Atmospheric vents

A Dual Check Valve with Atmospheric Vent shall be installed at
referenced cross-connections. Valve shall feature stainless steel
and rubber internals protected by an integral strainer. Primary
check shall be rubber to rubber seated, backed by the secondary
check with rubber to metal seating. The device shall be ASSE
approved under Std. 1012 and shall be a Watts Series 9D.

Available Models

Suffix:

S –

for

1

2

" (15mm) union end solder connections.

SC – for satin chrome finish

LU – less union

9D-M2

May also be installed vertically

Union outlet

Secondary
check valve

Rugged mesh

stainless strainer screen

Primary

check valve

Vent and drain

connections

Brass body construction and stainless working parts throughout

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-