Series 97FB-FSFE

UL/FM Fire Service Strainers

Sizes: 3" – 10" (80 – 250mm)

Series 97FB-FSFE (flanged) UL/FM Fire Service Strainers are

used in water spray fire protection systems to protect against

clogging that can be caused by particles fouling the discharge

opening of the sprinkler heads. Strainers for fire systems are

designed to trap foreign material

1

4

" diameter or larger.

This type of strainer is usually installed upstream of most

of the devices in the system including the meters, backflow

preventers (or detector check valves) and flow alarms, in order

to protect these devices from damage caused by dirt

and debris.

Features

• Fabricated steel, epoxy lined and coated

body and cover

• With cleanout port
• Large solids trap to minimize screen blockage
• 304 Stainless Steel strainer element

Pressure – Temperature

Suitable for supply pressure up to 175psi (12.1 bar)
Water temperature up to 140˚F (60˚C)

Materials

Body and cover: corrosion resistant fusion-bonded epoxy
lined and coated steel.
Screen: 304 Stainless Steel, .25 diameter perforation
Clean-Out Plug: Brass or Bronze
Flanges: AWWA Class “D”

For Fire Protection Applications

ES-97FB

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

97FB-FSFE

Listed 321

Class 5551

Approvals

Specifications

The strainer shall be designed to permit removal of the strainer

screen for replacement and repair without removing the body

from the line. A flush outlet shall be provided with each strainer.

The strainer screen shall withstand 125psi (8.6 bar) when

plugged. Friction loss shall not exceed 10psi (69 kPa) when

tested with foreign materials (gravel) equal to 2

1

2

' (762mm)

of filled pipe trapped in the strainer. Open screen area shall be

at least 6 times greater than the nominal pipe size open area.

Friction loss shall not exceed 3psi (21 kPa) at rated flow when

tested with clean strainer screen and clean water. The strainer

shall be a Watts Series 97FB-FSFE.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For
precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product
design, construction, specifications, or materials without prior notice and without incurring any obligation to make such
changes and modifications on Watts products previously or subsequently sold.

Advertising