Watts WattsBox User Manual

Wattsbox, Insulated enclosures, For outdoor installations

Advertising
background image

WattsBox

Insulated Enclosures

Specifications

Backflow prevention assemblies subjected to potential freezing con-

ditions shall be protected with the WattsBox enclosure as shown.
The enclosure shall be of reinforced aluminum construction, provid-

ing access through doors for testing/certification purposes. It must

also be totally removable for maintenance purposes. The enclosure

shall be structurally lined with a unicellular, non-wicking insula-

tion consisting of a sandwich laminate or applied by spray. It shall

contain a thermostatically controlled heat source mounted to the

interior wall or on the backflow preventer to provide protection to

-30°F. No wood or “particle board” shall be allowed in assembly.

Insulation mounted with glue will be cause for rejection. Power

source will be protected with a ground fault circuit interrupting

receptacle, UL Standard 943, NEMA 3R, installed by others, inside

the box.
The enclosure shall contain drain openings sized to accommodate

the maximum discharge of the reduced pressure zone assembly.

Drain openings shall open to discharge under the most severe

conditions. These openings are protected against intrusion of either

wind, debris or animal. The enclosure is provided with means of

permanent anchor and “lockable” access doors and/or lid to pro-

hibit theft or vandalism.
All “wet” portions of the backflow prevention assembly shall be

protected within the enclosure. Fire department hose connections

and OSY indicating valve handles shall be maintained outside the

enclosure.
The enclosure shall be factory assembled and delivered to the site

ready to install with no drilling, screwing or riveting of enclosure

required on site. The enclosure and the backflow preventer shall

be covered by a single warranty policy. Enclosure shall be a Watts

Series WattsBox.

For Outdoor Installations

ES-WB

Features

• Designed to eliminate valve vault entry requirements of OSHA

confined Space Ruling 29CFR 1910.146.

• Single source Watts Regulator warranty of the enclosure, the

backflow preventer, and the heat source.

• Allows for the installation of the backflow preventer “at the

service connection” in accordance with AWWA Standards.

• Is specifically designed to meet NFPA guidelines.

The enclosure provides freeze protection to maintain the water

supply to the property’s fire protection system. (NFPA 3-3.1.8

and 3.6.1.3.2).

• Strategically placed doors provide access to the backflow pre-

vention assembly for testing and repair without removal of the

entire unit.

• An economical alternative to expensive retrofit installations.
• Eliminates potential drainage constraints in existing equipment

rooms.

• Saves valuable floor space.
• Standardly furnished with thermostatically controlled heat source

for freeze protection down to -30°F.

• Contains no structural wood or particle board for long life.
• Easy installation aluminum enclosures feature interlocking panels

which eliminate the use of screws during assembly.

• Can be temporarily removed for replacement of the backflow

preventer without the need for replacement of freeze protection

services.

• ASSE 1060 Certified (Consult factory for approved models)

WattsBox Aluminum Enclosure

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

NOTICE

The information contained herein is not intended to replace the full

product installation and safety information available or the experi-

ence of a trained product installer. You are required to thoroughly

read all installation instructions and product safety information

before beginning the installation of this product.