Stainless Series

S513-14 or S6513-14 (Globe)

S1513-14 or S61513-14 (Angle)

Operation

The Watts ACV Deep Well Pump Control Valve with Pressure Relief Feature is designed to minimize the
surges associated with the starting and stopping of well pumps, and open, relieving excessive pressure,
during the pumping cycle. The valve slowly opens and closes as required to control pumping related surges.
The pump starts and stops against an open valve.

Pump start up: When the pump is signaled to start, the 4-Way Solenoid is energized and directs fluid and
pressure into the cover chamber (above the diaphragm), and relieves fluid and pressure from the power
chamber (below the diaphragm). The fluid and pressure relieved from the cover chamber is vented to
atmosphere or available floor drain. The valve closes at an adjustable rate, gradually admitting pumping
pressure into the distribution system. Rate of valve closure is controlled by the adjustable closing speed
control, which restricts the speed at which fluid and pressure evacuate the power chamber. The valve
remains closed during the pumping cycle.

Pressure Relief Feature: During the pumping cycle, the valve acts as a pressure relief valve. The valve,
which is closed during the pumping cycle, senses header pressure and quickly opens when header pressure
exceeds the pilot setting, relieving excess pressure. When header pressure is lowered below the pilot
setting, the valve closes.

Pump shutdown: When the pump is signaled to shut-off, the 4-Way Solenoid is de-energized, and directs
fluid and pressure into the power chamber (below the diaphragm), and relieves fluid and pressure from the
cover chamber (above the diaphragm). The fluid and pressure relieved from the cover chamber is vented
to atmosphere or available floor drain. The valve opens at an adjustable rate, gradually reducing pumping
pressure, allowing the system check valve to slowly close. Rate of valve opening is controlled by the
adjustable opening speed control, which restricts the speed at which fluid and pressure evacuate the cover
chamber. When the valve reaches the full open position, the limit switch is actuated, turning the pump off.

Manual Operation: Engaging the Solenoid Manual operator simulates power to the solenoid, manually
closing the main valve. Disengaging the Solenoid Manual operator returns the valve to the open position.

DEEP WELL PUMP CONTROL
VALVE with PRESSURE
RELIEF FEATURE