Installation, Maintenance, & Repair

Series 009 and LF009

Reduced Pressure Zone Assemblies

Sizes:

1

4

" – 3" (8 – 80mm)

RP/IS-009

3" (80mm) 009NRS

Testing

For field testing procedure, refer to Watts installation sheets

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on

www.watts.com.
For other repair kits and service parts, refer to our Backflow

Prevention Products Repair Kits & Service Parts price list PL-RP-

BPD found on

www.watts.com.

For technical assistance, contact your local Watts representative.

NOTICE

For Australia and New Zealand, line strainers should be installed

between the upstream shutoff valve and the inlet of the backflow

preventer.

Local building or plumbing codes may require modifications to

the information provided. You are required to consult the local

building and plumbing codes prior to installation. If this informa-

tion is not consistent with local building or plumbing codes, the

local codes should be followed.

Need for Periodic Inspection/Maintenance: This product must

be tested periodically in compliance with local codes, but at least

once per year or more as service conditions warrant.
If installed on a fire suppression system, all mechanical checks,

such as alarms and backflow preventers, should be flow tested and

inspected in accordance with NFPA 13 and/or NFPA 25.
Corrosive water conditions, and/or unauthorized adjustments or

repair could render the product ineffective for the service intended.

Regular checking and cleaning of the product’s internal components

helps assure maximum life and proper product function.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information

can result in death, serious personal injury, property

damage, or damage to the equipment.
Keep this Manual for future reference.

Installation Instructions

Series 009 and LF009
Indoors –

Figure 1

For indoor installations, it is important that the assembly be easily

accessible to facilitate testing and servicing. If it is lo cat ed in a line

close to a wall, be sure the test cocks are easily accessible. A drain

line and air gap (see literature ES-AG/EL/TC) should be piped from

the relief valve connection as shown, where evidence of discharge

will be clearly visible and so that water dam age will not occur.

Therefore, never install in concealed locations.

Figure 1

Air Gap

Main

Strainer

Meter

2

1

2

" – 3" (65-80mm) 009

12"

NOTICE

In an area where freezing conditions can occur, Series 009 and

LF009 should be installed above ground in an insulated enclosure.
Series 009 and LF009 must be installed in an ac ces si ble location

to facilitate testing and ser vic ing. A discharge line should be piped

from the air gap at the relief valve con nec tion making sure that

there is adequate drainage. Never pipe the discharge line directly

into a drainage ditch, sewer or sump. Series 009 and LF009

should never be in stalled where any part of the unit could become

submerged in standing water.

Outside –

Figure 2

In an area where freezing conditions do not occur, Series 009 and

LF009 can be installed outside. The most sat is fac to ry in stal la tion is

above ground and should be in stalled in this manner when ev er pos-

sible.
It is generally recommended that back flow preventers never be

placed in pits unless absolutely necessary and then only when

approved by local codes. In such cases, a modified pit installation

is preferred.

Now available, WattsBox

Insulated Enclosures,

for more information, send

for literature ES-WB.

Figure 2

WattsBox

12"