ASME Water Pressure Relief Valves

For Pressure Protection of Hot

Water Heating Boilers
Sizes:

3

4

" – 2" (20 - 50mm)

Series LF174A

Lead Free* cast copper silicon alloy body safety relief valves for

pressure protection only of all types of hot water heating boiler

equipment. Pressure range 50 to 150psi (3 - 10 bar) with cor-

responding high ratings from 950,000 to 14,370,000 BTU/hr.

Female inlet and outlet connections. Sizes

3

4

" - 2" (20 - 50mm).

The LF174A features Lead Free* construction to comply with

Lead Free* installation requirements.

Features

• Seat located above drain; water cannot be trapped and

sediment cannot foul seat.

• Non-mechanical seat-to-disc alignment will not stick

or freeze.

• Water seal of high temperature resisting material isolates

spring working parts from water during relief.

Specifications

Boiler Relief Valves

An ASME Section IV certified pressure relief valve shall be

installed on each boiler as noted. The valve shall have a BTU

rating in excess of the BTU rating of the boiler’s heating output.

Each hot water space heating boiler shall be equipped with a

pressure relief valve set to relieve below the maximum boiler

working pressure. The valve shall feature a raised seat and

non-mechanical disc alignment. Working parts and spring shall

be isolated from any discharge by a high temperature resis-

tant material. The valve shall be constructed using Lead Free*

cast copper silicon alloy material. Lead Free* boiler relief valve

shall comply with state codes and standards where applicable,

requiring reduced lead content. Valve shall be a Watts Series

LF174A.

Operation

As thermal expansion conditions develop, pressure builds up to

the setting of the relief valve. This will cause discharging of small

quantity of water.
Should operating controls fail, permitting runaway firing, the

boiler water may reach steam temperatures. The valve will then

open to discharge steam at the rate or faster than the boiler can

generate it, thus restoring system pressure to a safer level.

The discharge line must be the same size as the valve outlet,

and must pitch downward from the valve to a safe place for

disposal.
Valve lever must be tripped at least once a year to ensure that

waterways are clear. This device is designed for emergency

safety relief and shall not be used as an operating control.

For Hot Water Boiler Applications

ES-LF174A

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Series LF174A

Series LF174A

LEAD FREE

*

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

*The wetted surface of this product contacted by consumable water

contains less than 0.25% of lead by weight.