WS1TC & WS1.25 TC Manual

Refill Flow Control Assembly or Refill Port Plug

To clean or replace the refill flow control, pull out the elbow-locking clip and then pull straight up on the elbow. Replace the elbow
locking clip in the slot so that it is not misplaced. Twist to remove the white flow control retainer. The flow control can be removed
by prying upward through the side slots of the retainer with a small flat blade screwdriver.

Chemically clean the flow control or the white flow control retainer using dilute sodium bisulfite or vinegar. Do not use a wire brush.
If necessary, replace the flow control, o-ring on the flow control retainer, or the o-ring on the elbow.

Reseat the flow control so the rounded end is visible in the flow control. Reseat the white flow control retainer by pushing the
retainer into the elbow until the o-ring seats. Remove locking clip, push down on elbow to reseat and insert locking clip.

Do not use Vaseline, oils, or other unacceptable lubricants on o-rings. A silicone lubricant may be used on the o-ring on the elbow or
the white retainer.

Meter Plug

This control valve does not come equipped with a meter, instead a plug is installed. The plug should not need to be serviced.

To remove the meter plug assembly, unscrew the meter cap on the left side of the control valve. Pliers may be used to unscrew the
nut if necessary.

With the nut removed, a slot at the top of the meter plug is visible. Twist a flat blade screwdriver in the slot between the control
valve body and the meter plug. When the meter plug is part way out it is easy to remove the meter plug from the housing.

Do not use a wire brush to clean the meter plug. Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar.

Do not use Vaseline, oils, or other unacceptable lubricants on the o-ring. A silicone lubricant may be used on the black o-ring.

Reinsert the meter plug into the side slot. Hand tighten the nut. Do not use a pipe wrench to tighten nut.

Compliance Table

Application

Injector and/or Plug(s)

Main Piston

Regenerant

Piston

Stack

Body

WS1TC Downflow
Softener or Regenerating
Filter

Injector in “DN” hole, Plug
in “UP” hole

V3011

V3174

V3005

V3001 or

V3001-02 (Mixing)

WS1TC Backwash Only
Filter

Plug in “DN” and “UP”
holes, Install Refill Port Plug

V3011

None

V3005

V3001 or

V3001-02 (Mixing)

WS1.25TC Downflow
Softener or Regenerating
Filter (1.32" Distributor)

Injector in “DN” hole, Plug
in “UP” hole

V3407

V3174

V3430

V3020 or

V3020-01 (Mixing)

WS1.25TC Backwash
Only Filter (1.32"
Distributor)

Plug in “DN” and “UP”
holes, Install Refill Port Plug

V3407

None

V3430

V3020 or

V3020-01 (Mixing)

WS1.25TC Downflow
Softener or Regenerating
Filter (32mm Distributor)

Injector in “DN” hole, Plug
in “UP” hole

V3407

V3174

V3430

V3020-02 or

V3020-03 (Mixing)

WS1.25TC Backwash
Only Filter (32mm
Distributor)

Plug in “DN” and “UP”
holes, Install Refill Port Plug

V3407

None

V3430

V3020-02 or

V3020-03 (Mixing)

Two holes are labeled DN and UP. Check for compliance. See Table.

Push the plug(s) and/or injectors firmly in place, replace the screen and hand tighten the injector cap.