II. INSTALLATION INSTRUCTIONS FOR UNITS WITH ADAPTERS:

OIL LEVEL CONTROLLERS WITH

–9

(Universal adapter),

-

10

(Slotted universal adapter),

-12

(Pole mounted adapter) AND –

FS OPTIONS

Set the controller so that the centerline of the sight window corresponds to the desired oil level in the crankcase.

Mount the controller close to the crankcase and connect the hose from the ¾” outlet located on the controller to the crankcase.
NOTE: The outlet port on the oil level controller must be located below the oil level in the crankcase.

An equalizing line must be used between the controller and crankcase in order to equalize the pressure. The tubing must be a
minimum of 1/2” I.D. and must be kept under 2 feet. DO NOT loop this line. It must be trap free and self draining, with a
downward pitch flow by gravity.





























OIL LEVEL CONTROLLER WITH

–11

AND

–11-FS

OPTION (for Mechanical Lubricators): See Figure 3





OIL LEVEL CONTROLLER WITH

–14 AND –14 –FS

OPTION (White Compressor)

Remove the triangular blind flange located on the compressor and mount the controller assembly in its place.

NOTE: It is important to install a drain line between the drain outlet of the compressor and the controller.









Drill holes in the lubricator housing as shown, and mount

the controller with the inlet located on the top side using the
seal washers and mounting bolts provided.

Place the seal washers between the controller and the

lubricator housing.

Figure 3

Figure 2: Typical Mount of –9 Adapter