Engine Coolant System

With the engine cold, check the coolant level in the coolant

reservoir, seen inside the Control Panel door. Maintenance

instructions for engine coolant are found in the engine

operator’s manual.

Battery

Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set generator’s system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable to negative battery

terminal (indicated by NEGATIVE, NEG, or (-).

NOTICE

Failure to disconnect negative battery cable will result in

equipment failure.

DO NOT attempt to jump start the battery.
Damage to equipment resulting from failure to follow this

instruction will void warranty.


4. Charge battery with battery charger at 2 Amps until

battery holds 12 Volts.

WARNING

Storage batteries give off explosive hydrogen

gas during recharging.
Slightest spark will ignite hydrogen and cause

explosion.
Battery electrolyte fluid contains acid and is

extremely caustic.
Contact with battery contents will cause severe

chemical burns.
A battery presents a risk of electrical shock and

high short circuit current.

DO NOT dispose of battery in a fire.
DO NOT allow any open flame, spark, heat, or lit cigarette

during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, and rubber

gloves.
Remove watches, rings, or other metal objects.
Use tools with insulated handles.




NOTE: With the battery installed and utility power available

to the transfer switch, the battery receives a trickle charge

whenever the engine is not running. It may take up to

72 hours to fully charge a discharged battery with the trickle

charge. The trickle charge is not able to recharge a battery

that is completely discharged.

5. Connect negative battery cable to negative battery

terminal (indicated by NEGATIVE, NEG, or (-)).

6. Ensure hardware on both positive and negative battery

terminals is secure.

7. Reinstall 15 Amp fuse in control panel.

CAUTION

Installing the control panel’s 15A fuse could

cause the engine to start.

DO NOT install this fuse until all plumbing and wiring has

been completed and inspected.

8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.

Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Set control board System switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required.
4. Connect red battery cable to battery positive terminal

(indicated by POSITIVE, POS, or (+)).

5. Connect negative battery cable to negative battery

terminal (indicated by NEGATIVE, NEG, or (-).

6. Ensure hardware on both positive and negative battery

terminals is secure.

7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.

To Clean the Generator

NOTICE

Improper treatment of generator can damage it and

shorten its life.

DO NOT expose generator to excessive moisture, dust,

dirt, or corrosive vapors.
DO NOT insert any objects through cooling slots.

• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft, bristle brush to loosen caked on dirt, oil,

etc.

• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow

away dirt. Inspect cooling air slots and openings on

the generator. These openings must be kept clean and

unobstructed.