tekmar 363 Universal Reset Control Installation User Manual

Page 17

Advertising
background image

17 of 40

Copyright © D 363 -12/08

• If a tekmar Zone Control is used, run the wires from the Zone Control to the 363. Refer to the instructions supplied with the Zone

Control.

• Run wire from other system components (pumps, boiler, actuator motors, etc.) to the control.
• Run wires from the 120 V (ac) power to the control. Use a clean power source to ensure proper operation. Multi-strand 16 AWG

wire is recommended for all 120 V (ac) wiring due to its superior flexibility and ease of installation into the terminals.

STEP FOUR

ELECTRICAL CONNECTIONS TO THE CONTROL

The installer should test to confirm that no voltage is present at any of the wires. Push the

control into the base and slide it down until it snaps firmly into place.

Powered Input Connections

120 V (ac) Power

Connect the 120 V (ac) power supply to the

Power N and Power L terminals (6 and 7).

This connection provides power to the microprocessor and display of the control. As well,

this connection provides power to the

Boil P1 and Mix P2 terminals (8 and 11) from the

Power L terminal (7).

Mixing Demand

To generate a

Mixing Demand, a voltage between 24 V (ac) and 240 V (ac) must be

applied across the

Mix Demand terminals (1 and 2).

Boiler Demand

To generate a

Boiler Demand, a voltage between 24 V (ac) and 240 V (ac) must be applied

across the

Boil Dem and the Com Dem terminals (4 and 3).

DHW Demand

To generate an external DHW Demand, a voltage between 24 V (ac) and 240 V (ac) must

be applied across the

Setp / DHW and the Com Dem terminals (5 and 3).

Setpoint Demand

To generate a Setpoint Demand, a voltage between 24 V (ac) and 240 V (ac) must be

applied across the

Setp / DHW and the Com Dem terminals (5 and 3).

Caution: The same power supply must be used for both the DHW demand and setpoint

demand circuits since they share the

Com Dem terminals.

Output Connections

Boiler Pump Contact (Boil P1)

The boiler pump output terminal (8) on the 363 is a powered output. When the relay

contact in the 363 closes, 120 V (ac) line (L) is provided to the

Boil P1 terminal (8) from

the

Power L terminal (7). To operate the boiler pump, connect one side of the boiler pump

circuit to terminal 8 and the second side of the pump circuit to the neutral (N) side of the

120 V (ac) power supply.

DHW Pump / Valve Contact

The

DHW Pump / Valve terminals (9 and 10) are an isolated output in the 363. There is

no power available on these terminals from the control. These terminals are to be used

as a switch to either make or break power to the DHW pump or the DHW valve. Since this

is an isolated contact, it may switch a voltage between 24 V (ac) and 240 V (ac).

Mixing Pump Contact (Mix P2)

The mixing pump output terminal (11) on the 363 is a powered output. When the relay

contact in the 363 closes, 120 V (ac) line (L) is provided to the

Mix P2 terminal (11) from

the

Power L terminal (7). To operate the mixing pump, connect one side of the mixing

pump circuit to terminal 11 and the second side of the pump circuit to the neutral (N) side

of the 120 V (ac) power supply.

Boiler Contact

The Boiler terminals (12 and 13) are an isolated output in the 363. There is no power

available on these terminals from the control. These terminals are to be used as a switch

to either make or break the boiler circuit. When the 363 requires the boiler to fire, it closes

the contact between terminals 12 and 13.

6

7

N

L

Power

120 V (ac)

1

2

Mix

Demand

24 to 240 V (ac)

3

4

Com

Dem

Boil

Dem

24 to 240 V (ac)

3

4

Com

Dem

Boil

Dem

Setp/

DHW

5

24 to 240 V (ac)

12 13

Boiler

T T

T

T

N

L

Boil

P1

9 10

DHW

Pmp/Vlv

11

Mix

P2

8

7

6

Power

120 V (ac)

L

N

N

L

Boil

P1

8

7

6

Power

120 V (ac)

L

N

9 10

DHW

Pmp/Vlv

24 to 240 V (ac)

M

or

• 120 V (ac) to be provided from a 15 A circuit breaker and must have a circuit disconnect installed.
• Connect ground wires to ground bus bar in wiring area.

Advertising