tekmar 363 Universal Reset Control Installation User Manual

Page 34

Advertising
background image

34 of 40

Copyright © D 363 -

12/08

0 to 80˚F
(-18 to 27˚C)

Default = 45

°F (7°C)

363 Monitor Menu (2 of 3)

The highest temperature recorded at the mixing sensor since
this item was last cleared.

The highest temperature recorded at the boiler sensor since
this item was last cleared.

The lowest temperature recorded at the boiler sensor since
this item was last cleared.

The total number of Boiler Pump (P1) running hours since
this item was last cleared.

The lowest temperature recorded at the mixing sensor since
this item was last cleared.

The total number of Mixing Pump (P2) running hours since
this item was last cleared.

The highest recorded temperature of the domestic hot water
or thermal storage tank since this item was last cleared. This
information can be used to monitor the performance of the
alternate heat source for the mixing system.

The lowest recorded temperature of the domestic hot water
or thermal storage tank since this item was last cleared.

The total number of DHW pump or valve running hours since
this item was last cleared.

This item is an adjustable warning. If a DHW demand exists
continually for longer than this warning setting, the control will
display a warning message.

This item is an adjustable warning, that can only be viewed
if the 10K 1 item has been set to INDR. If the air temperature
measured by the indoor air sensor exceeds this setting, the
control will display a warning message.

This item is an adjustable warning, that can only be viewed
if the 10K 1 item has been set to INDR. If the air temperature
measured by the indoor air sensor drops below this setting,
the control will display a warning message.

0 to 255˚F
(-18 to 124˚C)

0 to 255˚F
(-18 to 124˚C)

0 to 9999 hr

0 to 255˚F
(-18 to 124˚C)

0 to 255˚F
(-18 to 124˚C)

0 to 9999 hr

0 to 255˚F
(-18 to 124˚C)

0 to 255˚F
(-18 to 124˚C)

0 to 9999 hr

0:10 to 20:00 hr, OFF

Default = OFF

50 to 150˚F
(10 to 66˚C)

Default = 110

°F (43°C)

• •

• •

3 to 40 min, OFF

Default = OFF

This item is an adjustable warning. If either the boiler or mixing
supply temperature does not begin to increase within the set
amount of time when required, the control will display a warning
message.

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

Note: To clear the recorded information in the specific Item field, press and hold and .