363 Adjust Menu (4 of 5)

C4

B1

B1

C1

C1

C1

C1

C1

C2

B1

The time delay the control can expect between the
time the boiler contact closes and the burner fires.

The thermal mass characteristics of the boiler that
is being used.

The differential that the control is to use when it is
operating the boiler.

The device that is being used to supply flow to the
heat exchanger in the DHW storage tank.

No Indirect DHW tank = NONE

The DHW storage tank’s temperature during the
Occupied period.

10K 2 = DHW
DHW THRU

≠ NONE

The DHW storage tank’s temperature during the
UnOccupied period.

DIP switch =

Setback

10K 2 = DHW
DHW THRU

≠ NONE

The minimum boiler supply temperature to the
DHW storage tank during the Occupied period.

10K 2

≠ DHW

DHW THRU

≠ NONE

Selects whether or not DHW will be generated
during the UnOccupied period.

DIP switch =

Setback

10K 2

≠ DHW

DHW THRU

≠ NONE

The portions of the heating system that the DHW
will have priority over.

DHW THRU

≠ NONE

The minimum boiler supply temperature when a
setpoint demand is present during the Occupied
period.

10K 2 = DHW,

OR

DHW THRU = NONE

0:00 to 3:00 min
(1 sec. increments)

Default = 0:10 min

LITE, MED, HEVY

Default = MED

AUTO, 2 to 42˚F
(1 to 23˚C)

Default = AUTO

NONE, PUMP, VALV

Default = PUMP

OFF, 70 to 190˚F
(OFF, 21 to 88˚C)

Default = 140

°F (60°C)

OFF, 70 to 190˚F
(OFF, 21 to 88˚C)

Default = 120

°F (49°C)

OFF, 100 to 220˚F
(OFF, 38 to 104˚C)

Default = 180

°F (83°C)

OFF, DHW XCHG

Occ

Default = OFF

NONE, MIX, B+M
(Boiler+Mixing)

Default = NONE

OFF, 70 to 220˚F
(OFF, 21 to 104˚C)

Default = 180

°F (82°C)

Occ

UnOcc

Occ

UnOcc

Occ

Actual

Setting

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field