tekmar 363 Universal Reset Control Installation User Manual

Page 30

Advertising
background image

30 of 40

Copyright © D 363 -

12/08

363 RTU Adjust Menu (1 of 1)

Section

The desired room air temperature during an
Occupied period for the mixing zones.
Note: There is only a

±3°F adjustment in the

LTD access level.

35 to 100˚F
(2 to 38˚C)

Default = 70

°F (21°C)

The desired room air temperature during an
UnOccupied period for the mixing zones.
Note: There is only a

±3°F adjustment in the

LTD access level.

DIP switch =

Setback

35 to 100˚F
(2 to 38˚C)

Default = 65

°F (18°C)

OFF, 0:20 to 8:00 hr

Default = OFF

Selects whether the RTU is to use its internal
air sensor.

OFF, AIR

Default = AIR

Occ

UnOcc

• •

• •

• •

• •

• •

The amount of morning boost.

DIP switch =

Setback

NONE, AIR

Default =

NONE

This item allows for remotely adding a 10K
sensor to the RTU. Applications are for
temperature averaging.

This item allows for remotely adding a third
10K air sensor to the RTU, or a 10K slab
sensor to measure slab temperature.
MIX MIN = OFF

(for Slab Sensor only)

The minimum target temperature at the slab
sensor when not in WWSD.

REMOTE 3 = SLAB

OFF, 35 to 120

°F

(OFF, 2 to 49

°C)

Default = 70

°F (21°C)

40 to 150

°F

(4 to 66

°C)

Default = 90

°F (32°C)

The maximum target temperature at the slab
sensor.

REMOTE 3 = SLAB

Actual

Setting

This item allows for remotely adding a
second 10K sensor to the RTU. Applications
are for temperature averaging.

B1

D1

B1

D1

A

D3

D3

NONE, AIR, SLAB

Default = NONE

NONE, AIR

Default =

NONE

LT

D

INST ADV

USER

RTU 062

RTU 063

Range

Access
Level

Description

Item Field

363 RTU Monitor Menu (1 of 1)

The highest outdoor air temperature recorded since this
item was last cleared.

To clear, press & hold the

UP & DOWN buttons

-67 to 149˚F
(-55 to 65˚C)

-67 to 149˚F
(-55 to 65˚C)

14 to 167˚F
(-10 to 75˚C)

14 to 167˚F
(-10 to 75˚C)

The lowest outdoor air temperature recorded since this
item was last cleared.

To clear press, & hold the

UP & DOWN buttons

The highest room air temperature recorded since this item
was last cleared.

To clear press, & hold the

UP & DOWN buttons

The lowest room air temperature recorded since this item
was last cleared.

To clear, press & hold the

UP & DOWN buttons

LT

D

INST ADV

USER

RTU 062

RTU 063

Range

Access
Level

Description

Item Field

Advertising