Tweco Thermal Arc TA 500 User Manual

Page 22

Advertising
background image

Installation

2-2

Manual No 0-0470

Input
Strain
Relief

Figure 2-C Power Supply Rear Panel. Input of

Primary Power Cables

Power

Transformer

(T1)

Line

Voltages

Accepted

Fuse or

Circuit

Breaker

Amperages

Recommended

Minimum

Primary Wire

1

230
460

450
225

400 MCM

2/0

2

460
575

225
170

2/0

1

3

220
380

450
250

400 MCM

3/0

Table 2-A Line Voltages, Circuit Protection and

Recommended Wire Size.

NOTE:

This information is based on the 1978 National
Electrical Code, Table 310-16. Larger sizes may
be required if the length exceeds 25 feet.

Ground Lug

Figure 2-D Ground Lug

WARNING

Do Not Turn On Power Until Step 37.

7. On the right-hand side of the power supply

base, about half-way back, are the connection
lugs for the output cables. Feed the two posi-
tive (RED) Work cables, (end with large hole in
lug), through the large plastic bushing on the
lower right hand side of the front panel. Con-
nect the cables to the positive (RED) output con-
nections. The other end of these cables are con-
nected to the work table.

8. Feed the two negative (GREEN) cables, (end

with large hole in lug), through the same plas-
tic bushing as the positive cables. Connect to
the negative (GREEN) output connection in the
Power Supply. The other end of these cables
will be connected to the Supply Console.

9. Replace the side panels and cover.