02 routine service and calibration requirements, Routine service and calibration requirements -2, Transtig 170pi – Tweco 170Pi Transtig User Manual

Page 58

Advertising
background image

TRANSTIG 170Pi

POWER SOURCE PROBLEMS AND ROUTINE SERVICE REQUIREMENTS 5-2 Manual 0-5241

10 Fault light is on, and E-1 is

shown on the Amps display

A Fail to Safe protection has

operated in STICK mode-

VRD fault.

A Reset mains power, if fault does not

clear then have an accredited CIG-

WELD service provider repair unit.

B Fail to Safe protection has

operated in TIG mode- In-

verter fault.

B Reset mains power, if fault does not

clear then have an accredited CIG-

WELD service provider repair unit.

C External voltage has been

applied to the welding

circuit.

C Reset mains power and remove the

source of the external voltage.

Table 5-1

5.02 Routine Service and Calibration Requirements

!

WARNING

There are extremely dangerous voltage and power levels present inside this Inverter Power Source.

Do not attempt to open or repair unless you are an accredited CIGWELD Service Provider. Discon-

nect the Welding Power Source from the Mains Supply Voltage before disassembling.

Routine Inspection, Testing & Maintenance
The inspection and testing of the power source and associated accessories shall be carried out in accordance

with Section 5 of AS 1674.2 - 2007: Safety in Welding and Allied Processes-Part 2 Electrical. This includes an

insulation resistance test and an earthing test to ensure the integrity of the unit is compliant with Cigweld's

original specifications.
If equipment is to be used in a hazardous location or environments with a high risk of electrocution as outlined

in AS 1674.2 - 2007, then the above tests should be carried out prior to entering this location.

A. Testing Schedule

1. For transportable equipment, at least once every 3 months; and
2. For fixed equipment, at least once every 12 months.

The owners of the equipment shall keep a suitable record of the periodic tests and a system of tagging,

including the date of the most recent inspection.

A transportable power source is deemed to be any equipment that is not permanently connected and fixed

in the position in which it is operated.

B. Insulation Resistance

Minimum insulation resistance for in-service Cigweld Inverter Power Sources shall be measured at a voltage

of 500V between the parts referred to in Table 6-1below. Power sources that do not meet the insulation

resistance requirements set out below shall be withdrawn from service and not returned until repairs have

been performed such that the requirements outlined below are met.

Advertising