Relays, Display, Relay setup – Monarch Instrument DC1250 User Manual

Page 29: Display - menu timeout

Advertising
background image

28

HOLD OFF

Use ▼▲ keys to enter time in seconds from Alarm till relays pull

in.

RESET DELAY

Use ▼▲ keys to enter time in seconds from RESET till relays drop

out.

LATCHING

Toggle using MENU - make alarm latching

LOCK OUT

DEFAULT


4.3 RELAYS

This option is used to program the physical relay outputs. There are two relays and each is
programmed independently. The relays can be assigned to one or more ALARM events or
the EXTernal INPUT. Use the Up Arrow (▲) or Down Arrow (▼) buttons to scroll and
highlight RELAYS.. and press the MENU button. The menu options are shown below.

RELAY 1

OFF

RELAY is OFF

ALARM 1

RELAY is tied to ALARM 1

ALARM 2

RELAY is tied to ALARM 2

ALARM 3

RELAY is tied to ALARM 3

ALARM 4

RELAY is tied to ALARM 4

EXT INPUT

Relay is tied to EXTernal INPUT

RELAY 2

same as RELAY 1

FAILSAFE

Relays are energized in the non alarm condition

NEITHER

Select Neither relay as failsafe

RELAY1

Select RELAY 1 as failsafe

RELAY2

Select RELAY 2 as failsafe

BOTH

Select both relays as fail safe


4.4 DISPLAY

This option is used to set up the display. The Window Configuration allows the user to
choose how to display data - either as a trend or as digital values or as a combination of
both. The time stamp that appears on the trend can be customized, the menu can be set to
disappear and have the display revert back to normal, and the backlight can be set to go off
after a period of inactivity. (The backlight will restore on any event.) Use

the Up Arrow (▲)

or Down Arrow (▼) buttons to scroll and highlight DISPLAY.. and press the MENU button.
The menu options are shown below.

WINDOW CONFIG

TREND

Set display to full screen TREND (both

Channels)

DUAL

DIGITAL

Set display to DUAL DIGITAL readouts

BOTTOM

DIGITAL

Set display to TREND in top half, DIGITAL in

lower half (CH B)

INV DIGITAL

Set DIGITAL display to WHITE characters on

DARK background.

ALARM BLINK

DIGITAL value will blink when in alarm

DIGITAL <-->

SWAP the position of dual digital windows.

TABLE OF CONTENTS

Advertising