Install the transformer, Connect the 24 volt low voltage wires, Low voltage wire size chart – Edge Lighting 600W/24V Remote Recessed Transformer User Manual

Page 2: Terminal tap chart

Advertising
background image

LOW VOLTAGE WIRE SIZE CHART

2

Install the Transformer

1: Select the location between the wall studs (16" apart) where
the transformer is to be mounted.

2: Place the transformer between the studs and fasten it to the
studs through the bracket holes with four #8 or #10 screws
(not provided).

A

STUD

COM

T2

T3

T4

T1

SCREW

BRACKET

2

Connect the 24 Volt Low
Voltage Wires

B

1: Install two THHN low voltage wires from the transformer
to the electrical box to which the power feed canopy will be
attached. Run the proper size wire using the "Low Voltage
Wire Size Chart" below.

2: Insert one low voltage wire into the secondary terminal
marked "COM" and tighten the screw firmly.

3: Insert the second low voltage wire to the "T2" tap terminal
(default) and tighten the screw firmly.

4: Measure the voltage at the power wires coming into the
transformer. If the voltage is not in the range of 115-120
volt, then pick the proper terminal tap using the "Terminal
Tap Chart" to reconnect the second low voltage wire.

5: Install drywall.

COM

T3

T4

T1

2

3

1

TERMINAL TAP CHART

PRIMARY POWER
INPUT VOLTAGE

TERMINAL TAP
TO BE USED

105-109

T4

110-114

115-120

121-125

T3

T2

T1

LOW VOLTAGE WIRES

TRANSFORMER
WATTAGE

WIRE SIZE
FOR 5 FT

WIRE SIZE
FOR 6-15 FT

WIRE SIZE
FOR 16-20 FT

WIRE SIZE
FOR 21-40 FT

600 WATT

#12 GA

#8 GA

#6 GA

#4 GA

NOTE: The THHN wire sizes specified in "Low Voltage Wire Size
Chart" are for 3% or less drop in voltage based on 600 watt

loads. Lengths are the distance from the

recessed

transformer

to the system power feed connector, or power feed canopy.

T2

ELECTRICAL BOX

NOTE: Using a smaller wire size other than specified will result in
a increase in voltage drop and will reduce the lamp intensity.