Connect the 120 volt wires – Edge Lighting 600W/24V Remote Recessed Transformer User Manual

Page 3

Advertising
background image

COM T

T2

T3

T4

T1

4

3

C

Connect the 120 Volt Wires

1: Install the 120 Volt power wires to the transformer.

2: Insert the hot power wire inline with the black transformer
wire into the 120 Volt terminal block and tighten the screw
firmly.

3: Insert the neutral power line wire inline with the white
transformer wire into the 120 Volt terminal block and tighten
the screw firmly.

4: Ground the transformer housing in accordance with local
electrical codes.

3

2

1

120 VOLT
TERMINAL BLOCK

HOT POWER WIRE

NEUTRAL POWER WIRE

D

5: After installing the entire low voltage system, if the lamps
have low intensity, then measure the voltage at the fixture
closest to the power feed contacts with a voltmeter. The
system must be at least 80% loaded and the voltmeter
should read between 22V-24V ~AC. If the voltage does not
fall in this range, call Edge Lighting "Technical Support" at
773-770-1195.

6: Operating the system for a few minutes, on the low
voltage side, all electrical connection points should be no
more than warm to the touch. If a connection is hot to the
touch, retighten the connection and check to ensure that
the temperature decreases.

7: Replace the transformer cover and tighten the four Phillips
screws on the front of the transformer.

COVER

7

PHILLIPS SCREW

7

7

7

Advertising