Removing the Rack Doors

See the procedures for removing doors in the documentation provided with your rack cabinet.

CAUTION:

Because of the size and weight of the rack cabinet doors, never attempt to remove or install

them by yourself.

CAUTION:

Store the doors where they will not injure someone if the doors accidently fall over.

Marking the Rack

For a 1-U system, you must allow 1 U (44 mm, or 1.75 inches) of vertical space for each system
you install in the rack.

Rack cabinets that meet EIA-310 standards have an alternating pattern of three holes per rack unit
with center-to-center hole spacing (beginning at the top hole of a 1-U space) of 15.9 mm, 15.9 mm,
and 12.7 mm (0.625 inch, 0.625 inch, and 0.5 inch) for the front and back vertical rails
(see Figure 1-3). Rack cabinets may have round or square holes.

NOTE:

The vertical rails may be marked by horizontal lines and numbers in 1-U increments. If you want,

you can make a note of the number marking on the rack’s vertical rail. It is not necessary to mark or place
tape on the rack.

Figure 1-3.

One Rack Unit

CAUTION:

If you are installing more than one system, install the mounting rails so that the first system

is installed in the lowest available position in the rack.

1 U (44 mm or 1.75 inches)

12.7 mm (0.5 inch)

15.9 mm (0.625 inch)

15.9 mm (0.625 inch)

12.7 mm (0.5 inch)