Information Update

www

.dell.com | support.dell.com

E0780

PROC n PRESENCE

Microprocessor is not installed
in socket n.

Install a microprocessor in
socket n. See "Replacing a
Processor" in your Installation
and Troubleshooting Guide.

E07F0

PROC n IERR

Faulty or improperly installed
microprocessor.

See "Troubleshooting the
Microprocessors" in your
Installation and Troubleshooting
Guide.

E07FA

PROC n THERMTRIP Specified microprocessor is out

of acceptable temperature range
and has halted operation.

See "Troubleshooting System
Cooling Problems" in your
Installation and Troubleshooting
Guide. If the problem persists,
ensure that the microprocessor
heat sinks are properly installed.
See "Replacing a Processor"
in your Installation and
Troubleshooting Guide.

NOTE:

The LCD continues to

display this message until the
system’s power cord is
disconnected and reconnected to
the AC power source, or the SEL
is cleared using either Server
Assistant or the BMC Management
Utility. See the Dell OpenManage
Baseboard Management
Controller User’s Guide for
information about these utilities.

E0876

PS n MISSING

PS n STATUS

No power available from the
specified power supply; specified
power supply is improperly
installed or faulty.

See "Troubleshooting Redundant
Power Supplies" in your
Installation and Troubleshooting
Guide.

E0876

PS n PREDICTIVE

Power supply voltage is out of
acceptable range; specified power
supply is improperly installed or
faulty.

See "Troubleshooting Redundant
Power Supplies" in your
Installation and Troubleshooting
Guide.

E0876

PS n AC LOST

PS n AC RANGE

Power source for specified power
supply is unavailable, or out of
acceptable range.

Check the AC power source
for the specified power supply.

Table 1-4.

LCD Status Messages (continued)

Line 1
Message

Line 2
Message

Causes

Corrective Actions