Step 7 — insulate the unit, Step 8 — complete electrical connections – Carrier AIR-COOLED CONDENSER UNITS 09BY006-024 User Manual

Page 11

Advertising
background image

3. A high-density fiberglass (2 lb minimum density) or semi-

rigid foamed insulation such as Styrofoam™ will be re-
quired inside the ducts to prevent air erosion. The insu-
lation must be firmly secured in the discharge duct near
the blower discharge to withstand the high air velocity.

Step 7 — Insulate the Unit —

The 09BY units are

not insulated. If the unit will be operated during cold weather
and the equipment room is not at outdoor temperatures, the
unit cabinet should be insulated to prevent condensation. In-
sulate the unit in the same manner as the ductwork insula-
tion described in Condenser Air Duct Insulation section on
page 10.

Step 8 — Complete Electrical Connections

IMPORTANT: Units may be used on 208, 230, 460,
or 575 v, 3-phase systems. As shipped from the fac-
tory, units are wired for 460 v or 575 v operation. If
the unit will be used on a 208 or 230 v system, rewire
the condenser fan motor prior to unit start-up. The 575-v
motor is connected to the proper voltage as shipped,
and all connections are internal to the motor.

To rewire the unit, disconnect and reconnect the wires at

the motor junction box as shown on the connection diagram
on the unit motor cover or in the unit wiring book.
GENERAL — Verify that nameplate electrical requirements
match available power supply. Voltage at condenser must be
within the minimum and maximum shown in Table 4 and
phases must be balanced within 2%. Contact local power com-
pany for line voltage corrections. Never operate a motor where
a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of volt-
age imbalance:
% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 240-3-60.

AB = 243 v
BC = 236 v
AC = 238 v

243 + 236 + 238

Average Voltage =

3

717

=

3

= 239 v

Table 4 — Electrical Data

UNIT

09BY

VOLTAGE

(3 Ph, 60 Hz)

SUPPLY VOLTAGE*

FAN

POWER SUPPLY

Min

Max

FLA

Hp

MCA

MOCP

006

208/230

187

254

7.5

2

9.4

15

460

414

508

3.4

4.3

15

575

518

632

2.7

3.4

15

008

208/230

187

254

10.5

3

13.6

20

460

414

508

4.8

6.0

15

575

518

632

3.9

4.9

15

012

208/230

187

254

10.5

3

13.6

20

460

414

508

4.8

6.0

15

575

518

632

3.9

4.9

15

014

208/230

187

254

16.7

5

20.9

35

460

414

508

7.6

9.5

15

575

518

632

6.1

7.6

15

016

208/230

187

254

16.7

5

20.9

35

460

414

508

7.6

9.5

15

575

518

632

6.1

7.6

15

024

208/230

187

254

30.8

10

38.5

60

460

414

508

14.0

17.5

30

575

518

632

11.0

13.8

20

LEGEND

FLA

Full Load Amps

MCA

Minimum Circuit Amps. Used for wire sizing.

(Complies with NEC Section 430-24.)

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

*Units are suitable for use on electrical systems where voltage sup-

plied to the unit terminals is within listed minimum and maximum
limits.

NOTES:
1. Maximum allowable phase imbalance: Voltage ± 2%; Amps ± 10%.
2. Maximum incoming wire size for power circuit is 2/0 max.

Fig. 10 — Placement of Duct Flanges on Units

09BY016 and 09BY024

11

Advertising