CHECK VOLTAGE IMBALANCE

IS CONDENSER MOTOR WIRED FOR CORRECT VOLTAGE?

(Y/N)

LINE-TO-LINE VOLTS:

AB

V

AC

V

BC

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

V

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

V

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

%

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!

CALL LOCAL POWER COMPANY FOR ASSISTANCE.

C. Start-Up

CHECK INDOOR (EVAPORATOR) FAN SPEED AND RECORD.

CHECK OUTDOOR (CONDENSER) FAN SPEED AND RECORD.

AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

OIL PRESSURE (Where Appropriate)
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING CONDENSER-AIR TEMP
LEAVING CONDENSER-AIR TEMP
EVAP ENTERING-AIR DB (dry bulb) TEMP
EVAP ENTERING-AIR WB (wet bulb) TEMP
EVAP LEAVING-AIR DB TEMP
EVAP LEAVING-AIR WB TEMP

COMPRESSOR AMPS:

CIRCUIT A (L1/L2)

/

CIRCUIT B (L1/L2)

/

CIRCUIT C (L1/L2)

/

NOTES:

----------------------------------------------------------------------------------------