FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation in-
structions included with the accessory. Locate thermostat as-
sembly on a solid wall in the conditioned space to sense av-
erage temperature in accordance with thermostat installation
instructions.

Route thermostat cable or equivalent single leads of col-

ored wire from subbase terminals to low-voltage connec-
tions on unit (shown in Fig. 16) as described in Steps 1-4
below.
NOTE: For wire runs up to 15 m (50 ft), use no. 18 AWG
(American Wire Gage) insulated wire (35 C minimum). For

15 to 23 m (51 to 75 ft), use no. 16 AWG insulated
wire (35 C minimum). For over 23 m (75 ft), use no. 14
AWG insulated wire (35 C minimum). See Table 3 for wire
conversions.
1. If unit is mounted on roof curb and accessory thru-the-

curb service plate connection is used, route wire through
connection plate.

2. Pass control wires through the hole provided on unit (see

connection D, Connection Sizes table, Fig. 5).

3. Feed wire through the raceway built into the corner post

to the 24-v barrier located on the left side of the control
box. See Fig. 17. The raceway provides the UL (U.S.A.
Standard) required clearance between high- and low-
voltage wiring.

4. Connect thermostat wires to screw terminals of low-

voltage connector. The connector plugs into the control
board and may be removed to make connection. Plug con-
nector back into the control board after making connec-
tion or unit will not operate.

HEAT ANTICIPATOR SETTINGS — Set first-stage heat an-
ticipator settings at 1.0. Set second-stage heat anti-
cipator settings at 0.6. For units with optional electric heat,
set anticipator for second stage as shown in Table 4.

Table 3 — American/European Wire Conversions

AMERICAN

EUROPEAN

Industry

Standard Size

American

Conversion

(mm

2

)

Industry

Standard

Size (mm

2

)

18 AWG

0.82

1.0

16 AWG

1.30

1.5

14 AWG

2.08

2.5

12 AWG

3.30

4.0

10 AWG

5.25

6.0

8 AWG

6.36

10.0

6 AWG

13.29

16.0

4 AWG

21.14

25.0

3 AWG

26.65

2 AWG

33.61

35.0

1 AWG

42.39

50.0

1/0 AWG

53.49

2/0 AWG

67.42

70.0

3/0 AWG

85.00

95.0

4/0 AWG

107.19

120.0

250 kcmil

126.64

150.0

300 kcmil

151.97

350 kcmil

177.90

185.0

400 kcmil

202.63

240.0

500 kcmil

253.29

300.0

600 kcmil

303.95

LEGEND

AWG — American Wire Gage
kcmil — Thousand Circular Mils

Fig. 14 — Conduit Installation

CONTROL WIRE
TERMINAL
BLOCK

BRACKET AND
CONDUIT DRIP
BOOT

SINGLE POINT
BOX MOUNTING
SCREWS

HEATER
MODULE
(LOCATION 1)

HEATER
MODULE
(LOCATION 2)

HEATER
MOUNTING
BRACKET

HEATER
COVERS

MANUAL RESET
LIMIT SWITCH
LOCATION
(HIDDEN)

HEATER
WIRING
LABEL

CENTER POST

EMT OR RIGID
CONDUIT
(FIELD-
SUPPLIED)

DISCONNECT
MOUNTING
LOCATION

SINGLE
POINT
BOX

MAIN
CONTROL
BOX

Fig. 15 — Component Location

Table 4 — Unit Voltage

220

400

Heater kW

Anticipator Setting

Part No. 50DJ901—

Heater kW

Anticipator Setting

Part No. 50DJ901—

9.5

0.3

711

10.5

0.3

681

14.6

0.3

601

12.5

0.3

631

22.7

0.6

611

21.0

0.3

641

29.3

0.6

621

25.0

0.3

651

38.8

0.9

711, 621*

31.5

0.6

681, 641*

43.9

0.9

711, 621*

37.5

0.6

631, 651*

*Requires 2 heater packages.

12

Advertising
This manual is related to the following products: