Table 6 — Fan Performance (SI), 50LJQ008 (50 Hz) — Horizontal Discharge Units

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

300

350

400

450

500

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

1100

7.9

0.35

9.4

0.50

10.6

0.68

11.7

0.85

12.7

1.03

13.6

1.25

14.4

1.46

14.9

1.69

15.1

1.92

15.0

2.15

1200

8.3

0.42

9.8

0.59

11.0

0.78

12.0

0.95

13.0

1.15

13.9

1.36

14.8

1.58

15.5

1.82

16.0

2.06

16.4

2.31

1300

8.8

0.51

10.2

0.69

11.3

0.88

12.4

1.08

13.3

1.28

14.2

1.49

15.0

1.72

15.8

1.96

16.5

2.21

17.1

2.47

1400

9.2

0.60

10.6

0.80

11.7

0.99

12.7

1.22

13.7

1.42

14.5

1.63

15.3

1.87

16.1

2.12

16.9

2.38

1500

9.7

0.71

11.0

0.91

12.1

1.12

13.0

1.35

14.0

1.59

14.8

1.81

15.6

2.04

16.4

2.30

1600

10.1

0.82

11.3

1.04

12.5

1.28

13.4

1.49

14.3

1.75

15.2

2.00

15.9

2.24

1700

10.6

0.93

11.8

1.20

12.9

1.44

13.8

1.67

14.7

1.92

15.5

2.20

Table 7 — Fan Performance (SI), 50LJQ012 (50 Hz) — Horizontal Discharge Units

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

300

350

400

450

500

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

1300

7.6

0.30

8.9

0.41

10.2

0.56

11.1

0.64

12.1

0.77

13.1

0.92

13.9

0.93

14.0

0.52

15.0

1.13

15.6

1.32

1400

8.0

0.40

9.3

0.51

10.5

0.64

11.4

0.75

12.4

0.88

13.3

1.01

14.1

1.11

14.6

0.96

15.4

1.32

16.0

1.42

1500

8.4

0.48

9.6

0.60

10.7

0.72

11.8

0.86

12.7

0.99

13.5

1.12

14.3

1.26

15.1

1.35

15.7

1.49

16.4

1.54

1600

8.8

0.58

10.0

0.69

11.1

0.82

12.1

0.96

12.9

1.10

13.8

1.24

14.5

1.38

15.3

1.54

16.0

1.64

16.7

1.72

1700

9.1

0.69

10.3

0.78

11.3

0.93

12.3

1.07

13.2

1.22

14.0

1.37

14.8

1.52

15.5

1.66

16.3

1.84

17.0

1.95

1800

9.5

0.81

10.7

0.90

11.7

1.05

12.6

1.20

13.5

1.36

14.3

1.52

15.0

1.67

15.8

1.83

16.4

1.99

17.2

2.17

1900

9.9

0.95

11.0

1.02

12.0

1.18

12.9

1.34

13.8

1.50

14.6

1.68

15.3

1.83

16.0

2.00

16.7

2.16

17.3

2.33

2000

10.3

1.11

11.4

1.17

12.3

1.32

13.2

1.48

14.1

1.66

14.9

1.83

15.6

2.01

16.3

2.18

17.0

2.36

17.6

2.53

2100

10.7

1.29

11.8

1.33

12.7

1.47

13.5

1.65

14.4

1.84

15.1

2.00

15.9

2.20

16.6

2.38

2200

11.2

1.48

12.1

1.51

13.1

1.64

13.9

1.83

14.6

2.01

15.4

2.20

16.2

2.38

2300

11.6

1.70

12.5

1.71

13.4

1.83

14.2

2.01

15.0

2.20

15.7

2.41

Table 8 — Fan Performance (SI), 50LJQ008 (50 Hz) — Vertical Discharge Units

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

300

350

400

450

500

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

1100

8.7

0.42

10.1

0.59

11.1

0.75

12.2

0.93

13.1

1.12

14.0

1.30

14.8

1.51

15.7

1.77

16.4

2.02

17.2

2.35

1200

9.3

0.52

10.5

0.69

11.6

0.87

12.6

1.05

13.5

1.26

14.3

1.46

15.1

1.66

15.9

1.88

16.7

2.14

17.4

2.44

1300

9.8

0.64

11.0

0.81

12.1

1.01

13.0

1.20

13.9

1.41

14.7

1.63

15.5

1.84

16.2

1.98

16.9

2.29

17.6

2.56

1400

10.4

0.77

11.5

0.94

12.6

1.16

13.5

1.37

14.3

1.58

15.1

1.80

15.9

2.04

16.6

2.27

17.3

2.51

1500

11.0

0.92

12.0

1.10

13.0

1.33

13.9

1.56

14.7

1.78

15.5

2.00

16.3

2.25

17.0

2.50

1600

11.6

1.08

12.6

1.28

13.5

1.50

14.4

1.76

15.2

2.00

16.0

2.23

16.7

2.47

1700

12.2

1.26

13.1

1.48

14.0

1.70

14.9

1.97

15.7

2.23

16.4

2.48

Table 9 — Fan Performance (SI), 50LJQ012 (50 Hz) — Vertical Discharge Units

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

300

350

400

450

500

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

r/s

BkW

1300

8.4

0.37

9.6

0.51

10.8

0.61

11.7

0.69

12.6

0.81

13.3

0.90

14.3

1.05

15.1

1.27

15.9

1.48

16.7

1.67

1400

8.8

0.46

10.0

0.59

11.1

0.71

12.0

0.82

12.9

0.93

13.7

1.04

14.5

1.17

15.4

1.35

16.2

1.56

16.8

1.75

1500

9.2

0.55

10.4

0.68

11.5

0.81

12.4

0.94

13.2

1.06

14.0

1.19

14.8

1.26

15.6

1.44

16.4

1.62

17.1

1.83

1600

9.7

0.65

10.8

0.79

11.8

0.93

12.8

1.07

13.6

1.19

14.4

1.33

15.1

1.46

15.8

1.59

16.5

1.72

17.3

1.91

1700

10.2

0.75

11.2

0.91

12.2

1.06

13.1

1.20

13.9

1.34

14.7

1.48

15.4

1.63

16.1

1.76

16.7

1.89

17.4

2.04

1800

10.6

0.87

11.7

1.05

12.6

1.20

13.5

1.35

14.3

1.51

15.0

1.65

15.7

1.80

16.4

1.95

17.1

2.10

17.7

2.24

1900

11.1

1.01

12.1

1.19

13.0

1.35

13.9

1.52

14.7

1.68

15.4

1.84

16.1

1.99

16.8

2.14

17.4

2.31

18.0

2.46

2000

11.6

1.16

12.5

1.35

13.4

1.52

14.3

1.69

15.0

1.86

15.8

2.04

16.5

2.21

17.1

2.36

17.7

2.53

2100

12.0

1.32

13.0

1.53

13.8

1.70

14.6

1.88

15.4

2.07

16.1

2.25

16.8

2.43

2200

12.5

1.50

13.4

1.71

14.3

1.91

15.1

2.09

15.8

2.29

16.5

2.48

2300

13.0

1.70

13.9

1.91

14.7

2.13

15.5

2.31

16.2

2.52

LEGEND

r/s

Wheel Speed (Revolutions per Second)

Bkw — Fan Shaft Power (kW)

NOTES:
1. Boldface indicates field-supplied drive required.

2.

indicates field-supplied motor and drive required.

3. Maximum usable output power (BkW) on the 50LJQ008 unit is 1.79

(2.40 Bhp) with standard 1.12 BkW (1.5 hp) motor. The maximum
usable output power (BkW) increases to 2.16 (2.90 Bhp) on the
50LJQ012 unit with standard 1.5 BkW (2 hp) motor. Extensive

motor and electrical testing on the Weathermaker I units ensures
that the full power range of the motor can be utilized with confi-
dence. Using the fan motors up to the power ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.

4. Use of field-supplied motor may affect wire sizing. Contact

Carrier representative to verify.

5. Values include losses for filters, unit casings and wet coils.
6. Motor drive range is 10.30 to 14.70 r/s (622 to 882 rpm) on the

50LJQ008 and 11.50 to 15.00 r/s (692 to 896 rpm) on the 50LJQ012.
All other r/s (rpms) will require a field-supplied drive.