Descriptions and corrective actions, Methods of receiving errors and messages 5-10 – Dell Powervault LTO6 User Manual

Page 46

Advertising
background image

Table 5-3. Methods of Receiving Errors and Messages

If the error or message was presented by...

Do this...

The system's display (if the tape drive is enclosed in a
library or autoloader)

Refer to the documentation for the system.

The tape drive's single-character display and the fault
LED flashes amber

See “Descriptions and Corrective Actions.” To determine
the meaning of the LED, see the “Front Panel” on page
1-4
section in the Introduction.

The tape drive's single-character display and the fault
LED is solid amber

See “Selecting a Diagnostic or Maintenance Function” on
page 5-1.
To determine the meaning of the fault LED
activity, see the “Front Panel” on page 1-4 section in the
Introduction.

SCSI log sense data (such as TapeAlert flags) or SCSI
drive sense data

See Table 5-5 on page 5-17 or “Descriptions and
Corrective Actions.”

The tape drive's error log

See “Descriptions and Corrective Actions.”

Descriptions and Corrective Actions

Table 5-4 gives descriptions of the errors and messages that pertain to the tape
drive, and tells what to do when you receive them.

Notice:

If the tape drive detects a permanent error and displays an error code

other than

0

, it automatically performs a dump of vital data to drive

memory. If you force a dump, the existing dump will be overwritten and
data will be lost. After you force a dump, do not turn off the power to the
tape drive or you may lose the dump data.

Table 5-4. Descriptions and Corrective Actions

The single-character display clears if you power-off the drive.

Code

Cause and Action

0

No error occurred and no action is required. This code displays:

v

When power is cycled (turned off, then on) to the tape drive

v

When diagnostics have finished running and no error occurred

Note:

The single-character display is blank during normal operation of the tape drive.

1

Cooling problem. The tape drive detected that the recommended operating temperature was
exceeded. Perform the following action:

1.

If a fan is present in the system, ensure that it is rotating and is quiet. If not, replace the
fan. (For instructions about replacing the fan, see your system's documentation.)

2.

Remove any blockage that prevents air from flowing freely through the tape drive.

3.

Ensure that the operating temperature and airflow is within the specified range (see
Chapter 6, “Specifications,” on page 6-1).

4.

If the proper voltages are being applied but the problem persists, contact Dell technical
support.

The error code clears when you power-off the tape drive or place it in maintenance mode.

5-10

Dell PowerVault LTO Tape Drive User's Guide