Operation

Control Screens

Table 5 describes the available control screens.

Table 5. Control Screens

Control Screens

Description

Go to Bypass

Transfers the UPS system to internal Bypass mode.

When the Go to Bypass command is issued, the screen immediately shows the
message for five seconds: Manual Bypass Command. The option then changes to
Go to Normal.

When the Go to Normal command is issued, the screen immediately shows the
message Normal Mode Command Sent for five seconds. The option then changes
to Go to Bypass.

Battery Test

Schedule Battery Test: yes | Cancel Battery test: no

Starts a manual battery test.

See “Testing Batteries” on page 59.

Reset Error State

Reset Alarms: yes | no

Manually clears any latched alarms, such as bad battery detected, overload, or DC
Bus OV/UV.

If a bad battery alarm was also active, reset the battery test status to “Not
Tested.”

Load Segments

Load segment 1: on | off

Load segment 2: on | off

These on/off commands override automatic load segment on/off controls made by
the Automatic Start Delay and Automatic On Battery Shutdown settings. See
“Configuring Load Segments” on page 47.

Restore Factory Settings

Restore Factory Settings: yes | no

Available only in Standby mode.

Restoring the factory settings:

S Returns all user-configurable EEPROM settings to default factory settings
S Resets all pending on/off commands
S Clears the Event Log and resets all time stamps
S Resets the battery test status
S Initiates the Self Diagnostics test