Transferring from bypass to normal mode, Retrieving the event log, Behavior on overload – Dell UPS 5600R User Manual

Page 46

Advertising
background image

46

|

Operation

Transferring from Bypass to Normal Mode

To transfer from Bypass to Normal mode:

1

Press the

button for longer than one second to go to the main menu selection and scroll down to

the Control menu using the button.

2

Press the

button to enter the Control menu.

3

Select Go to Normal.

The text on the screen changes to Normal Command Sent. The Normal mode icon

flashes,

indicating Normal mode.

Retrieving the Event Log

To retrieve the Event Log:

1

Press the

button for longer than one second to go to the main menu selection and scroll down to

the Event Log menu using the button.

2

Press the

button to enter the Event Log list.

3

Scroll through the listed events, notices, and alarms using either the

button or the button.

Behavior on Overload

See Table 7 for an explanation of how the UPS responds to an overload condition.

Table 7. Behavior on Overload

Overload Severity

Load Level

On Utility Power

On Battery

Level 1

100% to 101%

Overload alarm and supports
load indefinitely

Overload alarm and supports load until
low battery shutdown level is reached

Level 2

102% to 110%

Overload and Level 2
Overload alarms and
supports load indefinitely

Transfers to Fault mode in 12 seconds
(±1 sec) or when low battery shutdown
level is reached

Level 3

> 110%

Overload, Level 2 Overload,
and Level 3 Overload alarms
and supports load
indefinitely

Transfers to Fault mode in 300 ms to
1 sec