Dell UPS 5600R User Manual

Page 44

Advertising
background image

44

|

Operation

Table 6. Settings (continued)

Description

Default Setting

Available Settings

External Battery Modules (EBMs)

[0] [1]

See “Configuring the UPS for an EBM” on page 50.

0

Charger

[Enabled] [Disabled]

If Enabled, batteries charge normally.

If Disabled, the battery charger is off.

Enabled

Battery Charge % to Restart

[0%] [10%] [20%] [30%]...[100%]

When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0%, the feature is disabled.

0%

Battery Low Alarm

[Immediate] [2 min] [3 min] [5 min]

If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.

3 min

Automatic Battery Tests

[Enabled] [Disabled]

See “Running Automatic Battery Tests” on page 51.

Enabled

Reset Peak Consumption Watts

[No] [Yes]

If No, no action.

If Yes, the Peak Consumption Watts value is
cleared and the date and time stamp for this
statistic is set to the current date and time.

No

Reset Cumulative Consumption
kWh

[No] [Yes]

If No, no action.

If Yes, the Cumulative Consumption kWh value is
cleared and the date and time stamp for this
statistic is set to the current date and time.

No

Reset Peak Headroom Watts

[No] [Yes]

If No, no action.

If Yes, the Peak Headroom Watts value is cleared
and the date and time stamp for this statistic is set
to the current date and time.

No