Table 6. Settings (continued)

Description

Default Setting

Available Settings

Unsynchronized Transfers

[Enabled] [Disabled]

If Enabled, unsynchronized transfers to the Bypass
are allowed.

If Disabled, unsynchronized transfers to the Bypass
are not allowed.

NOTE:

The Qualify Bypass setting may overrule the

Unsynchronized Transfers setting.

Enabled

External Battery Module (EBM)

[0] [1]

See “Configuring the UPS for an EBM” on page 53.

0

Charger

[Enabled] [Disabled]

If Enabled, batteries charge normally.

If Disabled, the battery charger is off.

Enabled

Battery Charge % to Restart

[0 %] [10%] [20%] [30%]...[100%]

When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0, the feature is disabled.

0 %

Battery Low Alarm

[Immediate] [2 min] [3 min] [5 min]

If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.

If Immediate, the battery low alarm activates at the
same time as the “UPS on Battery” notice.

3 min

Automatic Battery Tests

[Enabled] [Disabled]

See “Running Automatic Battery Tests” on page 54.

Enabled

Reset Peak Consumption Watts

[No] [Yes]

If No, no action.

If Yes, the Peak Consumption Watts value is
cleared and the date and time stamp for this
statistic is set to the current date and time.

No

Reset Cumulative Consumption
kWh

[No] [Yes]

If No, no action.

If Yes, the Cumulative Consumption kWh value is
cleared and the date and time stamp for this
statistic is set to the current date and time.

No