Table 14. Battery

Configuration

3700W: (16) 12V, 7.2 Ah internal batteries; (16) 12V, 7.2 Ah EBM

4200W: (16) 12V, 7.2 Ah internal batteries; (16) 12V, 7.2 Ah EBM

Battery Type

CSB GP1272 7.2 Ah or YUASA NP7-12 7Ah

Voltage

3750W: 192 Vdc internal, 192 Vdc/30A EBM

4200W: 192 Vdc internal, 192 Vdc/30A EBM

Fuses

UPS: (1) 30A fuse

EBM: (1) 30A fuse

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

Charging

Approximately 4 hours to 90% usable capacity at nominal line and no

supplementary power supply load

Monitoring

Advanced monitoring for earlier failure detection and warning

Battery Runtimes*

3750W internal batteries: 5 minutes at full load/21 minutes at half load

4200W internal batteries: 5 minutes at full load/16 minutes at half load

3750W with one EBM attached: 14 minutes at full load/43 minutes at half load

4200W with one EBM attached: 11 minutes at full load/35 minutes at half load

*Battery runtimes are approximate and vary depending on the load configuration and battery charge.

Battery

DC/DC

Input
Filter

Output

Filter

Bypass

Charger

DC/AC

Inverter

AC/DC

Boost

Figure 30. Online UPS Block Diagram