Transferring from bypass to normal mode, Setting power strategy – Dell UPS 3750R User Manual

Page 28

Advertising
background image

48

|

Operation

Transferring from Bypass to Normal Mode

To transfer from Bypass to Normal mode:

1

Press the

button for one second to go to the main menu selection and scroll down to the

Control menu using the button.

2

Press the

button to enter the Control menu.

3

Select Go to Normal.

The text on the screen changes to Normal Command Sent. The Normal mode icon

flashes,

indicating Normal mode.

Setting Power Strategy

On the High Efficiency setting, the UPS operates normally on Bypass, transfers to inverter in < 10 ms
when utility power fails, and transfers back to Bypass in one minute after utility power returns. The
Bypass mode status icon box appears on the UPS status summary screen when the UPS transfers to
Bypass.

NOTE:

High Efficiency operation is available after one minute of stable power.

To set the power strategy:

1

Press the

button for one second to go to the main menu selection and scroll down to the

Settings menu using the button.

2

Press the

button to enter the Settings menu.

3

Use the button to scroll to Power Strategy and press the

button.

The current setting for the option flashes when selected.

4

Select High Efficiency, Normal, or Converter using the and buttons.

The default is High Efficiency.

5

Press the

button to confirm.