Crown Boiler BWC151 User Manual

Page 4

Advertising
background image

2

3

WARNING

Failure to vent this boiler in accordance with these instructions could cause flue gas to enter the building

resulting in severe property damage, personal injury, or death:

Use of the BWC boiler with CPVC/PVC venting requires a special vent kit available from Crown

Boiler Company. Do not attempt to vent the boiler using either CPVC/PVC without the use of the

appropriate vent kit called for in this manual.

Do not apply thermal insulation to vent pipe or fittings.

Do not interchange vent systems or materials unless otherwise specified.

Do not obtain combustion air from within the building.

Do not install a barometric damper, vent damper, or drafthood on this boiler.

Unless otherwise noted, the

use of CPVC is required where the vent pipe passes through enclosed

spaces and through wall penetrations.

Do not use cellular core PVC (ASTM F891).

Pitch the vent piping as called for in these instructions to prevent condensate from pooling in the

venting.

Starting at the boiler, the first 30” of straight pipe, and the first 90 degree elbow, in the vent system

must be CPVC. PVC may only be used in the vent system downstream of this CPVC piping.

A. Vent System Design

There are several different ways to vent BWC series boilers. This installation supplement covers installation of

those vent systems that employ CPVC and PVC plastic pipe. Refer to the BWC installation manual when installing a

vent system using stainless steel or concentric PPs venting.

When CPVC/PVC pipe is used, there are two basic ways to vent a BWC boiler, each having several variations:

• Horizontal (“Side Wall”) Twin Pipe Venting (Table 1.1) - Vent system exits the building through an outside

wall. Combustion air and flue gas are routed between the boiler and the terminal using separate pipes.

• Vertical Twin Pipe Venting (Table 1.12) - Vent system exits the building through a roof. Combustion air and

flue gas are routed between the boiler and the terminal using separate pipes.

All of these systems are considered “direct vent” because in all of them air for combustion is drawn directly from

the outdoors into the boiler. A description of all of these venting options are shown in Tables

1.1 and 1.12.

One of

the vent option columns in Tables

1.1 or 1.12

must match the planned vent and air intake system exactly. In addition,

observe the following guidelines:

CPVC/PVC Adaptor Kits

1.

- The use of CPVC/PVC venting on BWC boilers requires the use of a special kit. Each

kit consists of the following principle components:

Adaptor/s for the Vent and Intake Connections

30” Section of Straight CPVC Pipe

CPVC Elbow

(2) PVC Termination Tees

(2) Rodent Screens

(1 ea.) Can PVC/CPVC Primer and Cement

Part Numbers for each kit are shown in

Table 1.5

NOTE: Models BWC070, 090, 120 and 151 may be ordered from the factory with the above components

packaged in the boiler. When this is done the vent adaptor may be shipped installed on the boiler.

CAUTION

Moisture and ice may form on the surfaces around the vent termination. To prevent deterioration,

surfaces should be in good repair (sealed, painted, etc.).

Advertising
This manual is related to the following products: