Carrier TP-NHP User Manual

Page 34

Advertising
background image

32

Option 22 — High Cool Latch Temperature (only available if outdoor
sensor is present)
An outdoor sensor is required for high cool latch feature.
This selection is only available when Option 1 is set to H2, A2, or h2 and when

Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 80, 85,

90, 95, 100, 105, 110, On.
OF (off) — Cooling always starts in low stage (Y1) and stages up to high stage

(Y1 and Y/Y2) when demand is sufficient and staging timer constraints have

been satisfied.
80 to 110

_F (27 to 43_C) — Outdoor temperature above which both first and

second stages of the compressor are energized to satisfy all cooling demands.

When a cycle starts under a high cool latch, it will finish the cooling cycle on

high stage.
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all

cooling demands.
Default is OF (off).
Option 23 — High Heat Latch Temperature (only available if outdoor
sensor is present)
This selection is only available when Option 1 is set to H2, or h2 and Option 7

(zoning) is set to OF (off). Configuration settings are OF (off), 20, 25, 30, 35, 40,

45, 50, On.
OF (off) —Heating always starts in low stage (Y1) and stages up to high stage

(Y1 and Y/Y2) when demand is sufficient and staging timer constraints have

been satisfied.
20 to 50

_F (−7 to 10_C) — Outdoor temperature below which both first and

second stages of the compressor are energized to satisfy all heating demands.