33

When a cycle starts under a high heat latch, it will finish the heating cycle on

high stage.
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all

heating demands.
Default is OF (off).
Option 24 — Programmable/Non−Programmable
This selection allows the installer to configure the thermostat as either

programmable or non−programmable. Selections are P, nP.
Default is P (programmable models only).
Option 25 — Number of Programmable Periods
This selection allows the installer to configure the thermostat for two or four

periods per day. Two periods is a common commercial application and four

periods is more common for residential. This selection is not available if Option

24 has been set to nP to configure the thermostat for non−programmable

operation.
2 — Periods DAY and SLEEP are available
4 — Periods WAKE, DAY, EVE, and SLEEP are available.
Default is 4.
Option 26 — Minimum Cooling Setpoint
This selection allows the installer to configure the minimum cooling setpoint that

the user is allowed to set. The range is based on the value of the adjustable

deadband Option 11, such that the minimum of the range is 50

_F/10_C plus the

adjustable deadband and the maximum is 90

_F/32_C.

Default is 52

_F/11_C (based on the adjustable deadband default = 2).