Carrier 58MVP User Manual

Page 10

Advertising
background image

NOT ENOUGH COOLING AIRFLOW—Generally, this indicates the Y/Y2 thermostat lead is not properly
connected.

STEP

ACTION

YES

NO

GO TO

1.

Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed.
Wait a few sec for self test before proceeding to next step.

—

—

2

2.

Make sure thermostat is calling for cooling. If thermostat lead G is not connected, jumper across
thermostat terminals R and G.

—

—

3

3.

Make sure thermostat fan control is in AUTO position if equipped.

—

—

4

4.

Do you have 24v across Y/Y2 and Com on furnace control board?

8

5

—

5.

You have a defective thermostat, or a break in wiring between thermostat and furnace, or the Y/Y2
thermostat terminal is not wired to thermostat.

—

—

6

6.

Fix problem.

—

—

7

7.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

—

—

INDEX

8.

Are air conditioning select switches A/C set to proper tonnage as required by condensing unit? (See
Table 1.)

10

9

—

9.

Set air conditioning select switches A/C for proper tonnage as required by condensing unit. (See
Table 1.)

—

—

7

10.

Disconnect the G thermostat lead or jumper if used.

—

—

11

11.

Does blower motor turn off in 90 sec when G thermostat lead is disconnected?

12

13

—

12.

Replace furnace control board.

—

—

7

13.

Observe operation of furnace in cooling mode for 8 minutes.

—

—

14

14.

Does furnace operate properly in cooling mode?

15

16

—

15.

Make sure outdoor unit is properly charged. If it is, go to page number indicated in Index for
CLEANUP AND START-UP INSTRUCTIONS. If problem persists on an intermittent basis, replace
furnace control board. If problem still persists after replacing furnace control board, contact your dis-
tributor.

—

—

INDEX

16.

Does furnace abruptly go through a self-test sequence as blower comes up to speed?

17

24

—

17.

Do you have less than 17 vac between R and Com on furnace control board?

18

24

—

18.

Do you have less than 90 vac between P1 and P2 on furnace control board?

19

20

—

19.

Make sure the wire gage between main fuse box and furnace complies with wire size specification
in Installation, Start-Up, and Operating Instructions.

—

—

6

20.

Disconnect the R thermostat lead.

—

—

21

21.

Do you have less than 17 vac between R and Com on furnace control board?

22

23

—

22.

Replace transformer.

—

—

7

23.

Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor unit. It is
recommended that AWG No. 18 color-coded copper thermostat wire be used for lengths up to 100
ft. For wire lengths over 100 ft, use AWG No. 16 wire.

—

—

6

24.

Press down on microprocessor chip and make sure it is properly seated to furnace control board. If
it is, replace furnace control board.

—

—

6

Table 1—Air Conditioning (A/C) Airflow Setup Switch Position

AIR CONDITIONER

(TONS)

AIRFLOW

(CFM)

A/C SWITCH POSITION

ALLOWABLE FURNACE MODEL SETUP

A/C-1

A/C-2

A/C-3

040

060

080

080

100

120

Default

1200 or

2000

OFF

OFF

OFF

3 Tons

1200 CFM

3 Tons

1200 CFM

3 Tons

1200 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

1-1/2

600

ON

OFF

OFF

X

X

X

—

—

—

2

800

OFF

ON

OFF

X

X

X

X

X

X

2-1/2

1000

ON

ON

OFF

X

X

X

X

X

X

3

1200

OFF

OFF

ON

X

X

X

X

X

X

3-1/2

1400

ON

OFF

ON

X

X

X

X

X

X

4

1600

OFF

ON

ON

—

—

—

X

X

X

5

2000

ON

ON

ON

—

—

—

X

X

X

X—Indicates allowable selection.

10

Advertising