Carrier 58MVP User Manual

Page 31

Advertising
background image

4.

Observe operation of furnace for several minutes or until fault occurs.

5

5.

Does fault occur again?

9

6

6.

Does a different fault occur?

7

8

7.

Go to page number indicated in Index for fault code flashed.

INDEX

8.

Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.

INDEX

9.

Is collector box and inducer housing properly draining condensate?

11

25

10.

Fix problem.

8

11.

Are pressure switches wired correctly?

13

10

12.

Replace pressure switch assembly.

8

13.

Do you have 24v between C (Common) on low-pressure switch LPS and Com on furnace control
board?

15

14

14.

The YELLOW wire to low-pressure switch LPS is not making good connection. Repair wire or re-
place harness.

8

15.

Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. Turn
power on and wait a few sec for self test, then reconnect jumper across R, W/W1, and W2 thermo-
stat terminals.

16

16.

Do you have 24v between connector terminal PL2-2 and Com on furnace control board when fault
occurs?

21

18

17.

Replace furnace control board.

8

18.

Turn power off.

19

19.

Do you have continuity across terminal PL2-2 and N.O. (Normally Open) contact on low-pressure
switch LPS?

12

20

20.

The ORANGE wire from low-pressure switch LPS to furnace control board is not making good con-
nection or low gas pressure switch LGPS (when used) is open. Check propane line pressure if us-
ing LGPS otherwise repair wire or replace harness.

10

21.

Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals. Discon-
nect BROWN wire from N.O. (Normally Open) contact on high-pressure switch HPS. Turn power on
and wait a few sec for self test, then reconnect jumper across R and W/W1 thermostat terminals.

22

22.

Does a Fault Code 32 occur?

17

23

23.

Reconnect BROWN wire to N.O. (Normally Open) contact on high-pressure switch HPS.

24

24.

The problem may be caused by a sag in vent pipe. If this is not the problem and fault still occurs,
replace pressure switch assembly.

8

25.

The vent tube to drain trap, drain trap, or drain line is clogged.

10

31

Advertising