Fault code 43 – Carrier 58MVP User Manual

Page 30

Advertising
background image

43.

If possible, replace inducer wheel. Otherwise, replace inducer motor assembly.

—

—

8

44.

Is there any frost build-up on combustion-air inlet?

45

46

—

45.

The problem is caused by reversed vent and combustion-air pipes or some other moist air entering
combustion-air pipe.

—

—

14

→

46.

You have inadequate combustion-air supply. This may be caused by:
- Excessive restriction in combustion-air or vent pipe.
- Internal restriction in coupling box or secondary heat exchangers

—

—

14

→

47.

Replace pressure switch assembly.

—

—

70

→

48.

Is unit a trophy unit?

50

49

—

→

49.

Does fault occur before blower motor turns ON?

47

51

—

→

50.

Replace pressure switch assembly with pressure switch assembly used in NON-trophy models or
replace furnace control board. If you replace furnace control board make sure replacement control
has a date code of 9837 or later. Only replace the pressure switch assembly or the furnace control
board NOT both.

—

—

70

→

51.

Replace furnace control board.

—

—

70

52.

Turn power off and disconnect jumper wire across R and W/W1 thermostat terminals.

—

—

53

53.

Turn power on and wait several sec before proceeding to next step.

—

—

54

54.

Disconnect collector box tube to pressure switch assembly.

—

—

55

55.

Jumper R and W/W1 thermostat terminals on furnace control board.

—

—

56

56.

Does Fault Code 42 occur within 11 sec after a call for heat?

57

58

—

57.

Reconnect collector box tube to pressure switch assembly.

—

—

10

58.

Reconnect collector box tube to pressure switch assembly.

—

—

36

59.

Go to page number indicated in Index for CLEANUP AND STARTUP INSTRUCTIONS. If problem
persists on an intermittent basis, contact your distributor.

—

—

INDEX

60.

Turn power off and disconnect jumper wire across R and W/W1 thermostat terminals.

—

—

61

61.

Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur-
nace control board.

—

—

62

62.

Does fault occur a few sec after high-pressure switch HPS makes?
NOTE: Check for 24v between the N.O. (Normally Open) contact on high-pressure switch
HPS and Com on furnace control board to know when high-pressure switch HPS makes.

63

67

—

63.

Turn power off and disconnect jumper wire across R, W/W1, and W2 thermostat terminals.

—

—

64

64.

Connect 1 side of a slope manometer with a tee to collector box pressure tap. Connect other side
with a tee to gas valve air pressure fitting. Refer to pressure check diagram in Appendix C.

—

—

65

65.

Turn power on and wait several sec, then jumper R, W/W1, and W2 thermostat terminals on fur-
nace control board.

—

—

66

66.

Do you have more than 1.9 in. wc pressure drop across heat exchangers when high-pressure
switch HPS makes?
NOTE: Check for 24v between the N.O. (Normally Open) contact on high-pressure switch
HPS and Com on furnace control board to know when high-pressure switch HPS makes.

47

44

—

→

67.

Does fault occur a few sec after main burners ignite?

63

68

—

→

68.

Observe operation of furnace in high heat for next 8 minutes or until fault occurs.

—

—

69

→

69.

Does the fault occur?

22

59

—

→

70.

If problem still persists check for internal restriction in coupling box or secondary heat exchangers.

—

—

14

Fault Code 43

PRESSURE SWITCH CALIBRATION FAULT—Indicates low-pressure switch LPS and high-pressure switch
HPS "make" points during high-heat purge are not within calibration range. This is determined by reading
inducer motor RPM when low-pressure switch LPS and high-pressure switch HPS make. Then the following
comparison is made:

0.55

‹

RPM (low)

RPM (high)

‹

0.90

If this relationship is not within range specified, furnace control board starts flashing fault colde 43, shuts unit
down (inducer runs for 15 sec), waits 2 minutes, stops flashing fault code, and restarts heating cycle.
It can also indicate that the high-pressure switch HPS made before the low-pressure switch LPS during either
low-heat or high-heat purge.

STEP

ACTION

YES

NO

GO TO

1.

Turn power off, remove blower access panel, and disconnect all thermostat leads from furnace con-
trol board.

—

—

2

2.

Turn power on and depress door switch. Use a piece of tape to hold switch closed.

—

—

3

3.

Jumper R, W/W1, and W2 thermostat terminals on furnace control board.

—

—

4

30

→