Convenience

Outlet

GFCI

Pwd-CO

Fuse

Switch

Pwd-CO

Transformer

Disconnect

Access Panel

C10857

Fig. 24 -- Convenience Outlet Location

Non--powered type: This type requires the field

installation of a general--purpose 125--volt 15--A circuit

powered from a source elsewhere in the building. Observe

national and local codes when selecting wire size and

conduit requirements, fuse or breaker requirements and

disconnect switch size and location. Route 125--v power

supply conductors into the bottom of the utility box

containing the duplex receptacle.

Unit--powered type: A unit--mounted transformer is

factory--installed to stepdown the main power supply

voltage to the unit to 115--v at the duplex receptacle. This

option also includes a manual switch with fuse, located in

a utility box and mounted on a bracket behind the

convenience outlet; access is through the panel beneath

the control box. See Fig. 24.

The primary leads to the convenience outlet transformer

are not factory--connected. Selection of primary power

source is a customer--option. If local codes permit, the

transformer primary leads can be connected at the

line--side terminals on the unit--mounted non--fused

disconnect switch; this will provide service power to the

unit when the unit disconnect switch is open. Other

connection methods will result in the convenience outlet

circuit being de--energized when the unit disconnect

switch is open. See Fig. 26. On a unit without a

unit--mounted disconnect, connect the source leads to the

main terminal block (TB1).

If the convenience outlet transformer is connected to the

line side of a field disconnect, the conduit provided with

the unit must be used to protect the wire as they are routed

from the transformer to the field disconnect. The end of

the conduit with the straight connector attaches to the

field disconnect. The other end does not need to connect

to the transformer; however, the conduit must be routed so

that all wiring is either in the conduit or behind the access

panel.

If the convenience outlet transformer is connected to the

line side of the factory disconnect option, route the wires

through the web bushing located on the bottom of the

disconnect box. For the load side wiring to the factory

option disconnect, route the wires through the hole on the

right side of the disconnect. Be sure to create a drip loop

at least 6” long.

2.0

50HE501288

NOTICE/AVIS

Convenience Outlet Utilization

Maximum Intermittent Use 15 - Amps

Maximum Continuous Use 8 - Amps

Observe a 50% limit on the circuit

Loading above 8 - Amps

Utilisation de la prise utilitaire

Usage intermittent maximum 15 - Amps

Usage continu maximum 8 - Amps

Observez une limite de 50% sur le circuit

Chargement au-dessus de 8 - Amps

C10077

Fig. 25 -- Convenience Outlet Utilization Notice

Test the GFCI receptacle by pressing the TEST button on

the face of the receptacle to trip and open the receptacle.

Check for proper grounding wires and power line phasing

if the GFCI receptacle does not trip as required. Press the

RESET button to clear the tripped condition.

C08283

UNIT

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER

TERMINALS

208,

230

240

L1: RED +YEL

L2: BLU + GRA

H1 + H3

H2 + H4

460

480

L1: RED

Splice BLU + YEL

L2: GRA

H1

H2 + H3

H4

575

600

L1: RED

L2: GRA

H1

H2

Fig. 26 -- Unit Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman

“Fusetron” T--15, non--renewable screw--in (Edison base)

type plug fuse.

50TC

--

*16