PremierLinkt (Factory Option)

C08199

Fig. 39 -- PremierLink Controller

NOTE:

Refer to Form 33CS--67SI for complete

PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual
available at unit start--up.
The PremierLink controller (see Fig. 39) is compatible

with Carrier Comfort Networkr (CCN) devices. This

control is designed to allow users the access and ability to

change factory--defined settings, thus expanding the

function of the standard unit control board. CCN service

access tools include System Pilot (TM), Touch Pilot (TM)

and Service Tool. (Standard tier display tools Navigatort

and Scrolling Marquee are not suitable for use with latest

PremierLink controller (Version 2.x).)

The PremierLink control is factory--mounted in the

50TC--D16 unit’s main control box to the left of the

Central Terminal Board (CTB). Factory wiring is

completed through harnesses connected to the CTB. Field

connections are made at a 16--pole terminal block (TB3)

located on the bottom shelf of the unit control box in front

of the PremierLink controller. The factory--installed

PremierLink control includes the supply--air temperature

(SAT) sensor. The outdoor air temperature (OAT) sensor is

included in the FIOP/accessory EconoMi$ert2 package.

(See page 40 for accessory enthalpy controls.)

The PremierLink controller requires the use of a Carrier

electronic thermostat or a CCN connection for time

broadcast to initiate its internal timeclock. This is

necessary for broadcast of time of day functions

(occupied/unoccupied).
NOTE: PremierLink controller is shipped in Sensor mode.
To be used with a thermostat, the PremierLink controller
must be configured to Thermostat mode. Refer to

PremierLink Configuration instructions for Operating Mode.

C11191

Fig. 40 -- 50HC**14 Control Box Component Locations -- PremierLink Controller Location

50TC

--

*16