Typical Installation

Figure 1

Figure 2

Installation Instructions

1. Consult local codes for specific installation requirements and restrictions

applicable to your area. It is recommended that system supply pressure

be at least 20psi (133kPa).

2. These instructions apply to series 825YD, and 826YD size 2

1

2

" to 10"

(65-250mm) only. The valves may be installed only in the horizontal ori-

entation as shown.

3. The valve assembly must be installed where it is accessible for periodic

testing and maintenance. Clearances shown in the installation views

apply to exterior, interior and pit/vault installations and are only recom-

mendations. These minimums do not apply to removable protective

enclosures. Refer to local codes for actual requirements in your area.

4. PRIOR TO INSTALLING THE VALVE INTO THE LINE, FLUSH THE

SUPPLY LINE OF ALL FOREIGN MATERIAL. Failure to flush the supply

line may cause the check valves to become fouled and require disas-

sembly and cleaning.

5. DO NOT LIFT THE ASSEMBLY BY CONNECTING TO THE GATE

VALVE HANDWHEELS OR STEMS.

6. After installation SLOWLY fill the assembly with water and bleed air

from the body using the #2, # 3 and # 4 test cocks. Test the valve

assembly to ensure correct operation.

NOTE: All assemblies are tested at the factory for proper operation and

leakage. If the valve does not pass the field test, it is most likely due to

a fouled check valve. This is not covered by the factory warranty. The

valve cover(s) must be removed and the check seats inspected and

cleaned. Any damage or improper operation caused by pipeline debris or

improper installation/start-up is not included in the factory warranty.

In case of a possible warranty claim, contact your local supplier or

FEBCO Representative. DO NOT REMOVE THE VALVE ASSEMBLY

FROM THE PIPELINE.

7. The assembly must be protected from freezing and excessive pressure

increases. Pressure increases can be caused by thermal expansion or

water hammer. These excessive pressure situations must be elimi-

nated to protect the valve and system from possible damage.

IS-F-825YD-826YD

I N S T A L L A T I O N I N S T R U C T I O N S

Series 825YD, 826YD

Reduced Pressure Zone Assemblies

Reduced Pressure Detector Assemblies

Sizes: 2

1

2

" – 10" (65 – 250mm)

FRT

RWWP

175

4

FRT

RWWP

175

4

826YD

12" (300mm) Minimum

Refer to Local Codes

12" (300mm)

Minimum

HORIZONTAL INSTALLATION OF THE RP SERIES 825YD

(Side View)

(Shown With Strainer)

FLOW

HORIZONTAL INSTALLATION OF THE RP SERIES 825YD

(Top View)

(Shown With Strainer)

18" (450mm) Min

6" (150mm) Minimum

Refer to Local Codes