LEGEND AND NOTES FOR FIG. 55

AHA

— Adjustable Heat Anticipator

C

— Contactor, Compressor

CAP

— Capacitor

CC

— Cooling Compensator

CLO

— Compressor Lockout

COMP — Compressor Motor
D

— Diode

EC

— Enthalpy Control

ECON — Economizer
EPS

— Emergency Power Supply

EQUIP — Equipment
ER

— Economizer Relay

FPT

— Freeze-Protection Thermostat

FSS

— Filter-Status Switch

FU

— Fuse

GND

— Ground

GVR

— Gas Valve Relay

HPS

— High-Pressure Switch

HS

— Hall-Effect Sensor

HV

— High Voltage

I

— Ignitor

IDM

— Induced-Draft Motor

IFC

— Indoor (Evaporator) Fan Contactor

IFM

— Indoor (Evaporator) Fan Motor

IGC

— Integrated Gas Unit Controller

LED

— Light-Emitting Diode

LPS

— Low-Pressure/Loss-of-Charge Switch

LS

— Limit Switch

MGV

— Main Gas Valve

MTR

— Motor

OAT

— Outdoor-Air Thermostat

OFM

— Outdoor (Condenser) Fan Motor

P

— Plug

PL

— Plug Assembly

QT

— Quadruple Terminal

R

— Relay

RS

— Rollout Switch

SAT

— Supply-Air Thermostat

SEN

— Sensor

SW1

— Switch Fully Open

SW2

— Switch Fully Closed

SW3

— Switch Minimum Vent Position

SW4

— Switch Maximum Vent Position

TC

— Thermostat-Cooling

TH

— Thermostat-Heating

TRAN — Transformer

Field Splice

Marked Wire

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Splice (Marked)

Factory Wiring

Field Control Wiring

Field Power Wiring

Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.

NOTES FOR FIG. 55

1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its

equivalent.

2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostats: HH07AT170, 172

Subbase: HH93AZ176, 177, 178 and 179

4. Set heat anticipator at .14 amp for first stage and .14 amp for second stage.
5. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from

230 v tap and connect to 208 v tap (RED). Insulate end of 230 v tap.