6table 1 — physical data (cont) – Carrier 48HJD005-007 User Manual

Page 6

Advertising
background image

6

Table 1 — Physical Data (cont)

LEGEND

*Single phase/three phase.

†Indicates automatic reset.

**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.

48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005-
007 (150,000 Btuh Heat input) units have 3 burners.

††An LP kit is available as an accessory.

||Three-phase standard models have heating inputs as shown. Single-phase

standard models have one-stage heating with heating input values as follows:

48HJE004, 48HJD005,006 — 72,000 Btuh
48HJF004, 48HJE005,006 — 115,000 Btuh
48HJF005,006 — 150,000 Btuh

***California compliant three-phase models.

†††California SCAQMD compliant low NO

x

models have combustion products that

are controlled to 40 nanograms per joule or less.

BASE UNIT 48

HJE/F/H/K/M/N004

HJD/E/F/G/H/K/L/M/N005

HJD/E/F/G/H/K/L/M/N006

HJD/HJE/HJF007

FURNACE SECTION

Rollout Switch Cutout Temp (F)†

195

195

195

195

Burner Orifice Diameter (in. ...drill size)**

Natural Gas — Std

HJE .113...33

HJD .113...33

HJD .113...33

HJD .113...33

HJF .113...33

HJE .113...33

HJE .113...33

HJE .113...33

—

HJF .129...30

HJF .129...30

HJF .129...30

HJH .113...33

HJG .113...33

HJG .113...33

—

HJK .113...33

HJH .113...33

HJH .113...33

—

—

HJK .129...30

HJK .129...30

—

HJM .102...38

HJL .102...38

HJL .102...38

—

HJN .102...38

HJM .102...38

HJM .102...38

—

—

HJN .116...32

HJN .116...32

—

Liquid Propane — Alt††

HJE .089...43

HJD .089...43

HJD .089...43

HJD .089...43

HJF .089...43

HJE .089...43

HJE .089...43

HJE .089...43

—

HJF .102...38

HJF .102...38

HJF .102...38

HJH .082...45

HJG .089...43

HJG .089...43

—

HJK .082...45

HJH .089...43

HJH .089...43

—

—

HJK .102...38

HJK .102...38

—

HJM .082...45

HJL .082...45

HJL .082...45

—

HJN .082...45

HJM .082...45

HJM .082...45

—

—

HJN .094...42

HJN .094...42

—

Thermostat Heat Anticipator Setting (amps) 208/230/460 v

First Stage

.14

.14

.14

.14

Second Stage

.14

.14

.14

.14

Gas Input (Btuh)

First Stage/Second Stage

HJE|| 50,000/ 72,000

HJD|| 50,000/ 72,000

HJD|| 50,000/ 72,000

HJD|| 50,000/ 72,000

HJF|| 82,000/115,000

HJE|| 82,000/115,000

HJE|| 82,000/115,000

HJE|| 82,000/115,000

—

HJF|| 120,000/150,000

HJF|| 120,000/150,000

HJF|| 120,000/150,000

HJH*** —/ 72,000

HJG*** —/ 72,000

HJG*** —/ 72,000

—

HJK***—/115,000

HJH*** —/115,000

HJH*** —/115,000

—

—

HJK*** —/150,000

HJK*** —/150,000

—

HJM††† —/ 60,000

HJL††† —/ 60,000

HJL††† —/ 60,000

—

HJN††† —/ 90,000

HJM††† —/ 90,000

HJM†††—/ 90,000

—

—

HJN††† —/120,000

HJN††† —/120,000

—

Efficiency (Steady State) (%)

HJE 82

HJD 82

HJD 82

HJD 82

HJF 81

HJE 81

HJE 81

HJE 81

—

HJF 80

HJF 80

HJF 80

HJH 82

HJG 82

HJG 82

—

HJK 81

HJH 81

HJH 81

—

—

HJK 80

HJK 80

—

HJM 81

HJL 81

HJL 81

—

HJN 81

HJM 81

HJM 81

—

—

HJN 82

HJN 82

—

Temperature Rise Range

HJE 15-45

HJD 15-45

HJD 15-45

HJD 15-45

HJF 55-85

HJE 35-65

HJE 35-65

HJE 35-65

—

HJF 50-80

HJF 50-80

HJF 50-80

HJH 15-45

HJG 15-45

HJG 15-45

—

HJK 55-85

HJH 35-65

HJH 35-65

—

—

HJK 50-80

HJK 50-80

—

HJM 20-50

HJL 20-50

HJL 20-50

—

HJN 30-60

HJM 30-60

HJM 30-60

—

—

HJN 40-70

HJN 40-70

—

Manifold Pressure (in. wg)

Natural Gas — Std

3.5

3.5

3.5

3.5

Liquid Propane — Alt††

3.5

3.5

3.5

3.5

Maximum Static Pressure (in. wg)

1.0

1.0

1.0

1.0

Field Gas Connection Size (in.)

1

/

2

1

/

2

1

/

2

1

/

2

HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief

450 ± 50

Cutout

428

Reset (Auto.)

320

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE

SWITCH (Liquid LIne) (psig)
Cutout

7 ± 3

Reset (Auto.)

22 ± 5

FREEZE PROTECTION THERMOSTAT

Opens (F)

30 ± 5

Closes (F)

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

1...20 x 24 x 1

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Bhp — Brake Horsepower