320IS Plus Installation Manual - EDP Commands

49

DIGOUT

Digital output

NONE, 1-4

RELNUM

Relative setpoint number

1-8

START

Starting setpoint

1-8

END

Ending setpoint

1-8

BATCHNG

Batching mode

OFF, AUTO, MANUAL

Command

Description

Values

DIGIN1
DIGIN2
DIGIN3
DIGIN4

Digital input function

OFF, ZERO, TARE, NT/GRS, UNITS, DSPTAR, PRINT, CLRCN,
KBDLOC, HOLD, BATSTA, BATPAU, CLRTAR, CLRACC, ACCUM,
ENTER, BATRUN, GROSS, NET, PRIM, SEC, NEWID

Table 5-10. DIG IN EDP Commands

EDP digital output commands only function in TEST mode (see Figure 8-4 on page 70).

Command

Description

DON#n

Set digital output n on

DOFF#n

Set digital output n off

DOFF#0

Set all digital outputs off

DON#0

Set all digital outputs on

For commands ending with “#n”, n is the digital output (1–4) being set on or off.

Table 5-11. DIG OUT EDP Commands

Command

Description

Values

AO1.SOURCE

Analog output source

GROSS, NET

AO1.OFFSET

Zero offset

0%, 20%

AO1.ERRACT

Error action

FULLSC, HOLD, ZEROSC

AO1.MIN

Minimum value tracked

0–999 990

AO1.MAX

Maximum value tracked

0–999 990

AO1.TWZERO

Zero calibration

0–65535

AO1.TWSPAN

Span calibration

0–65535

Table 5-12. ALGOUT 1 EDP Commands

Command

Description

Values

AO2.SOURCE

Analog output source

GROSS, NET

AO2.OFFSET

Zero offset

0%, 20%

AO2.ERRACT

Error action

FULLSC, HOLD, ZEROSC

AO2.MIN

Minimum value tracked

0–999 990

AO2.MAX

Maximum value tracked

0–999 990

AO2.TWZERO

Zero calibration

0–65535

Table 5-13. ALGOUT 2 EDP Commands

Command

Description

Values

Table 5-9. SETPNT EDP Commands