HST SERIES CONNECTED TO AN R8184G WITH THE APPLIANCE

BURNER MOTOR LESS THAN 3 AMPS @ 120 VAC

NOTES: The Power Venter is usually interlocked with the primary control of the appliance. Wire all other fur-
nace/boiler controls as normally done when conventional venting before continuing. Disconnect power from
the appliance before attempting to interlock the Power Venter.

1. Disconnect the BLACK burner motor wire from the ORANGE wire of the R8184G.
2. Reconnect the BLACK burner motor wire to the YELLOW wire in the Power Venter electrical box.
3. Connect the ORANGE wire from R8184G to the ORANGE and BLUE wires in Power Venter electrical box.

NOTE: Ignition transformer will continue to be attached to the ORANGE of the cad cell relay.

4. Connect the WHITE/BROWN wire in Power Venter electrical box to the WHITE wire on the burner motor.
5. Connect the BLACK wire in Power Venter to L1.
6. Connect both WHITE wires in the Power Venter to L2.

HSUL SERIES CONNECTED TO A 24V GAS HONEYWELL

SMART VALVE (SV9500 - SV9600 SERIES)

NOTE:
Power Venter may operate indepen-
dently of burner circuit when power
is initially supplied to L1 and L2 con-
nections of the Relay/Timer. If the
Power Venter continues to operate
for more than 10 minutes without a
call for heat, verify that wiring is in
accordance with proper diagram.